126 Parameters
No.
Name/Value
19.17
Local control disable
No
Yes
20
20 Start/stop/direction
20.01
Ext1 commands
not used
In1 Start
In1 Start; In2 Dir
Description
Enables/disables local control (start and stop
buttons on the control panel, and the local controls on
the PC tool).
WARNING! Before disabling local control,
ensure that the control panel is not needed for
stopping the drive.
Local control enabled.
Local control disabled.
Start/stop/direction and run/start/jog enable signal
source selection; positive/negative reference enable
signal source selection.
For information on control locations, see section
Local and external control locations
Selects the source of start, stop and direction
commands for external control location 1 (EXT1).
20.02
See also parameters
20.21
for the determination of the actual direction.
No start or stop command sources selected.
The source of the start and stop commands is
selected by parameter
state transitions of the source bits are interpreted as
follows:
(20.03)
State of source 1
0 - > 1 (
20.02
Edge)
=
20.02
Level)
1 (
=
0
The source selected by
start signal; the source selected by
source
determines the direction. The state
transitions of the source bits are interpreted as
follows:
State of source 1
(20.03)
0
0 - > 1 (
20.02
Edge)
=
20.02
Level)
1 (
=
26
(page
20.05
...
. See parameter
20.03 Ext1 in1 source
. The
Command
Start
Stop
20.03 Ext1 in1 source
is the
20.04 Ext1 in2
State of source 2
Command
(20.04
)
Any
0
forward
1
Start reverse
Default
FbEq 16
No
0
1
).
In1 Start; In2
Dir
0
1
2
Stop
Start