ABB ACS280 Firmware Manual page 379

Coldplate drives
Hide thumbs Also See for ACS280:
Table of Contents

Advertisement

Fieldbus control through the embedded fieldbus interface (EFB)
Parameter
58.76
RPDO1 COB-ID
58.82
RPDO6 COB-ID
58.88
RPDO21 COB-ID
58.77
RPDO1 transmission type
58.83
RPDO6 transmission type
58.89
RPDO21 transmission type
58.78
RPDO1 event timer
58.84
RPDO6 event timer
58.90
RPDO21 event timer
58.79
TPDO1 COB-ID
58.85
TPDO6 COB-ID
58.91
RPDO21 COB-ID
58.80
TPDO1 transmission type
58.86
TPDO6 transmission type
58.92
TPDO21 transmission type
58.81
TPDO1 event timer
58.87
TPDO6 event timer
58.93
TPDO21 event timer
Setting for
fieldbus control
1 (default) for
58.76), 0 (default
for
58.82
and
58.88)
255 (default)
0 (default)
1 (default for
58.79), 0 (default
for
58.85
and
58.91)
255 (default)
100 (default for
58.81)
0 (default for
58.87, 58.93)
Function/Information
Defines the COB-ID for the PDO
and also enables or disables it.
0= Disable this PDO
1= Enable this PDO with default
COB-ID
other= Enable this PDO with
given (COB-ID)
Defines the transmission type of
the PDO.
0 = acyclic synchronous
1...240 = cyclic synchronous
254...255 = asynchronous
Defines the time-out time for the
PDO.
0 = no timeout
other = if this PDO is enabled and
not received for event timer
milliseconds, 58.14
Communication loss action is
performed
Note: The timeout supervision is
activated upon a successful
reception of the RPDO.
Defines the COB-ID for the PDO
and also enables or disables it.
0 = Disable this PDO
1 = Enable this PDO with default
COB-ID
other = Enable this PDO with
given COB-ID
Defines the transmission type of
the PDO.
0 = acyclic synchronous
1...240 = cyclic synchronous
252 = synchronous RTR only
253 = asynchronous RTR only
254...255 = asynchronous
Defines the time-out time for the
PDO.
0 = no timeout
other = if this PDO is enabled and
has not been transmitted for
event timer milliseconds, a
transmission is forced
379