No.
Name/Value
31.14
Number of trials
0...5
31.15
Total trials time
1.0...600.0 s
31.16
Delay time
0.0...120.0 s
31.19
Motor phase loss
No action
Fault
31.20
Earth fault
No action
Warning
Fault
31.21
Supply phase loss
No action
Fault
Description
Defines the maximum number of automatic resets
that the drive is allowed to attempt within the time
defined by parameter
If the fault persists, subsequent reset attempts will
be made at intervals defined by
The faults to be automatically reset are defined by
31.12 Autoreset selection
Number of automatic resets.
Defines a time window for automatic fault resets. The
maximum number of attempts made during any
period of this length is defined by
trials
.
Note: If the fault condition remains and cannot be
reset, each reset attempt will generate an event and
start a new time window. In practice, if the specified
31.14
number of resets (
take longer than the value of
continue to attempt resetting the fault until the cause
is eventually removed.
Time for automatic resets.
Defines the time that the drive will wait after a fault
before attempting an automatic reset. See parameter
31.12 Autoreset selection
Autoreset delay.
Selects how the drive reacts when a motor phase loss
is detected. See section
(parameter 31.19)
on page
No action taken.
The drive trips on fault
Selects how the drive reacts when an earth (ground)
fault or current unbalance is detected in the motor or
the motor cable.
No action taken.
The drive generates an
The drive trips on fault
Selects how the drive reacts when a supply phase loss
is detected.
No action taken.
Note: When this option is selected, the drive will
eventually overheat or the supply bridge may be
damaged if one supply phase is lost, unless 50%
derating is done when dimensioning the system.
The drive trips on fault
31.15 Total trials time
.
31.16 Delay time
.
31.14 Number of
) at specified intervals (
31.15
, the drive will
.
Motor phase loss detection
78
.
3381 Output phase loss
A2B3 Earth leakage
warning.
2330 Earth leakage
.
3130 Input phase loss
Parameters 191
Default
FbEq 16
0
.
10 = 1
30.0 s
31.16
)
10 = 1 s
0.0 s
10 = 1 s
Fault
0
.
1
Fault
0
1
2
Fault
0
.
1