No.
Name/Value
Temp sensor 1
excitation
Abs motor speed used
Abs motor speed %
Abs output frequency
Abs motor torque
Abs output power
Abs motor shaft power
External PID1 out
AO1 data storage
Other
13.13
AO1 forced value
-
13.16
AO1 filter time
0.000 ... 30.000 s
Description
The output is used to feed an excitation current to the
temperature sensor 1, see parameter
Temperature 1 source
. See also section
protection
.
01.61 Abs motor speed used
01.62 Abs motor speed %
01.63 Abs output frequency
01.64 Abs motor torque
01.65 Abs output power
01.68 Abs motor shaft power
71.01 External PID act value
13.91 AO1 data storage
Terms and abbreviations
Source selection (see
Forced value that can be used instead of the selected
output signal. See parameter
selection
.
Defines the filtering time constant for analog output
AO1.
%
Unfiltered signal
100
63
Filtered signal
T
-t
/T
O = I × (1 - e
I = filter input (step)
O = filter output
t
= time
T = filter time constant
Filter time constant.
35.11
Motor thermal
13.02 AO force
t
)
Parameters 121
Default
FbEq 16
20
26
27
28
30
31
32
33
37
).
-
0.000 V
1000 = 1 -
0.100 s