140 Parameters
No.
Name/Value
21.08
DC current control
Bit
Name
0
DC hold
1
Post-
magnetization
2
DC brake
3...15
Reserved
0b0000...0b1111
21.09
DC hold speed
0.00...1000.00 rpm
21.10
DC current reference
0.0...100.0%
21.11
Post magnetization
time
0...3000 s
21.13
Autophasing mode
Turning
Description
Activates/deactivates the DC hold and post-
magnetization functions. See section
magnetization
on page
Note: DC magnetization causes the motor to heat up.
In applications where long DC magnetization times
are required, externally ventilated motors should be
used. If the DC magnetization period is long, DC
magnetization cannot prevent the motor shaft from
rotating if a constant load is applied to the motor.
Value
1 = DC hold. See section
Note: The DC hold function has no effect if the start signal is
switched off.
1 = Post-magnetization. See section
52
.
Note: Post-magnetization is only available when ramping is the
selected stop mode (see parameter
1 = Enable DC brake.
DC magnetization selection.
Defines the DC hold speed in speed control mode. See
21.08 DC current control
parameter
hold
51
on page
.
DC hold speed.
Defines the DC hold current in percent of the motor
nominal current. See parameter
control
DC magnetization
, and section
After 100 s post-magnetization time, the maximum
magnetization current is limited to the magnetization
current corresponding to the actual flux reference.
DC hold current.
Defines the length of time for which post-
magnetization is active after stopping the motor. The
magnetization current is defined by parameter
DC current reference
.
21.08 DC current control
See parameter
Post-magnetization time.
Selects the way autophasing is performed during the
Autophasing
ID run. See section
This mode gives the most accurate autophasing
result. This mode can be used, and is recommended,
if the motor is allowed to rotate during the ID run and
the start-up is not time-critical.
DC
51
.
DC hold
51
on page
.
Post-magnetization
21.03 Stop mode
, and section
21.08 DC current
on page
46
on page
.
Default
FbEq 16
0b0000
on page
).
1 = 1
5.00 rpm
DC
See par.
46.01
30.0%
51
.
1 = 1%
0 s
21.10
1 = 1 s
Turning
0