ABB ACS280 Firmware Manual page 201

Coldplate drives
Hide thumbs Also See for ACS280:
Table of Contents

Advertisement

No.
Name/Value
Low falling
High rising
32.16
Supervision 2 action
No action
Warning
Fault
Fault if running
32.17
Supervision 2 signal
32.18
Supervision 2 filter time
0.000 ... 30.000 s
32.19
Supervision 2 low
-21474830.00...
21474830.00
32.20
Supervision 2 high
-21474830.00...
21474830.00
32.21
Supervision 2
hysteresis
0.00...100000.00
Description
Action is taken whenever the signal falls from a value
higher than the Supervision 1 low limit + 0.5 *
hysteresis to a value which is lower than the
Supervision 1 low limit - 0.5 * hysteresis.
Action is deactivated when the signal rises to higher
than the Supervision 1 low limit + 0.5*hysteresis.
Note: Supervision action is also deactivated for every
motor start command.
Action taken whenever the signal rises from a value
lower than the Supervision 1 high limit - 0.5 *
hysteresis to a value which is higher than the
Supervision 1 high limit + 0.5 * hysteresis.
Action is deactivated when the signal falls to lower
than the Supervision 1 high limit - 0.5 * hysteresis.
Note: Supervision action is also deactivated for every
motor start command.
Selects whether the drive generates a fault, warning
or neither when the value monitored by signal
supervision 2 exceeds its limits.
Note: This parameter does not affect the status
32.01 Supervision status
indicated by
No warning or fault generated.
A8B0 Signal supervision
Warning
The drive trips on fault
The drive trips on fault
running.
Selects the signal to be monitored by signal
supervision function 2.
For the available selections, see parameter
Supervision 1 signal
.
Defines a filter time constant for the signal monitored
by signal supervision 2.
Signal filter time.
Defines the lower limit for signal supervision 2.
Low limit.
Defines the upper limit for signal supervision 2.
Upper limit.
Defines the hysteresis for the signal monitored by
signal supervision 2.
Note: This parameter applies to all selections of
32.15
parameter
, not just Hysteresis.
Hysteresis.
.
is generated.
80B0 Signal supervision
80B0 Signal supervision
32.07
Parameters 201
Default
FbEq 16
8
9
No action
0
1
.
2
if
3
Current
0.000 s
1000 = 1 s
0.00
-
0.00
-
0.00
-