198 Parameters
No.
Name/Value
Both
Abs both
Hysteresis
Low falling
High rising
32.06
Supervision 1 action
No action
Warning
Fault
Description
Action is taken whenever the signal is above the
Supervision 1 high limit + 0.5 * hysteresis or below
the Supervision 1 low limit - 0.5*hysteresis.
Action is deactivated whenever the signal is in
between the Supervision 1 high limit - 0.5 * hysteresis
and the Supervision 1 low limit + 0.5 * hysteresis.
Action is taken whenever the absolute value of the
signal is above the absolute value of the Supervision 1
high limit + 0.5 * hysteresis or below the absolute
value of the Supervision 1 low limit - 0.5 * hysteresis.
Action is deactivated whenever the absolute value
of the signal is in between the absolute value of the
Supervision 1 high limit - 0.5 * hysteresis and the
absolute value of the Supervision 1 low limit + 0.5 *
hysteresis.
Action is taken whenever the signal is above the
Supervision 1 high limit + 0.5 * hysteresis.
Action is deactivated whenever the signal is below
the Supervision 1 low limit - 0.5 * hysteresis.
The status is unchanged when the signal value is
in between the Supervision 1 high limit + 0.5 *
hysteresis and the Supervision 1 low limit - 0.5 *
hysteresis.
Action is taken whenever the signal falls from a value
higher than the Supervision 1 low limit + 0.5 *
hysteresis to a value which is lower than the
Supervision 1 low limit - 0.5 * hysteresis.
Action is deactivated when the signal rises to higher
than the Supervision 1 low limit + 0.5*hysteresis.
Note: Supervision action is also deactivated for every
motor start command.
Action taken whenever the signal rises from a value
lower than the Supervision 1 high limit - 0.5 *
hysteresis to a value which is higher than the
Supervision 1 high limit + 0.5 * hysteresis.
Action is deactivated when the signal falls to lower
than the Supervision 1 high limit - 0.5 * hysteresis.
Note: Supervision action is also deactivated for every
motor start command.
Selects whether the drive generates a fault, warning
or neither when the value monitored by signal
supervision 1 exceeds its limits.
Note: This parameter does not affect the status
32.01 Supervision status
indicated by
No warning or fault generated.
A8B0 Signal supervision
Warning
The drive trips on fault
.
is generated.
80B0 Signal supervision
Default
FbEq 16
5
6
7
8
9
No action
0
1
.
2