ABB ACS280 Firmware Manual page 345

Coldplate drives
Hide thumbs Also See for ACS280:
Table of Contents

Advertisement

Code
Fault / Aux. code
(hex)
64B2
User set fault
64E1
Kernel overload
6581
Parameter system
6681
EFB comm loss
Programmable fault:
58.14
Communication loss
action
6682
EFB config file
6683
EFB invalid
parameterization
6684
EFB load fault
6685
EFB fault 2
6686
EFB fault 3
6882
Text 32-bit table
overflow
6885
Text file overflow
7081
Control panel loss
Programmable fault:
49.05
Communication loss
action
7082
I/O module comm
loss
Cause
Loading of user parameter
set failed because
• requested set does not
exist
• set is not compatible with
control program
• drive was switched off
during loading.
Operating system error.
Parameter load or save
failed.
Communication break in
embedded fieldbus (EFB)
communication.
Embedded fieldbus (EFB)
configuration file could not
be read.
Embedded fieldbus (EFB)
parameter settings
inconsistent or not
compatible with selected
protocol.
Embedded fieldbus (EFB)
protocol firmware could not
be loaded.
Version mismatch between
EFB protocol firmware and
drive firmware.
Fault reserved for the EFB
protocol application.
Fault reserved for the EFB
protocol application.
Internal fault.
Internal fault.
Control panel or PC tool
selected as active control
location for drive has ceased
communicating.
Communication between IO
module and drive is not
working properly.
Fault tracing 345
What to do
Ensure that a valid user parameter set
exists. Reload if uncertain.
Reboot the control unit (using
96.08 Control board boot
parameter
or by cycling power. If the problem
persists, contact your local ABB
representative
Try forcing a save using parameter
96.07 Parameter save manually
Check the status of the fieldbus
master (online/offline/error etc.).
Check cable connections to the
EIA-485 terminals 25, 26, 27 and 28 on
the control unit.
Contact your local ABB representative.
Check the settings in parameter group
58 Embedded fieldbus
Contact your local ABB representative.
Check the documentation of the
protocol.
Check the documentation of the
protocol.
Reset the fault. Contact your local ABB
representative if the fault persists.
Reset the fault. Contact your local ABB
representative if the fault persists.
Check PC tool or control panel
connection.
Check control panel connector.
Disconnect and reconnect the control
panel.
Replace the drive.
)
. Retry.
.