9
TROUBLESHOOTING
9.5.3 Error codes E400
communication)
Error Code
E400
The FDL address of the target DP-Slave is out of the range.
H
The FDL address specified for the target DP-Slave belongs
E401
H
to the local station (QJ71PB92V).
E402
The read data length is incorrect.
H
E403
Read error response.
H
E404
The slot number is incorrect.
H
E405
The index is incorrect.
H
E406
The CommRef number is incorrect.
H
Class1 service of Acyclic communication was executed while
E407
H
I/O data exchange is stopped.
A physical execution error detected, or system switching
E410
H
occurred during service execution in the redundant system.
E411
Execution error on the protocol was detected.
H
E412
Execution error on the application was detected.
H
E420
Read error was detected on the DP-Slave side.
H
E421
Write error was detected on the DP-Slave side.
H
E422
Module error was detected on the DP-Slave side.
H
E423
Processing on the DP-Slave side is not available.
H
E424
Application error was detected on the DP-Slave side.
H
Request-not-supported error was detected on the DP-Slave
E425
H
side.
E426
Incorrect index was detected on the DP-Slave side.
H
E427
Incorrect data length was detected on the DP-Slave side.
H
E428
Incorrect slot number was detected on the DP-Slave side.
H
E429
Incorrect data type was detected on the DP-Slave side.
H
Access to an access-disabled area was attempted from the
E42A
H
DP-Slave side.
E42B
Access is not available on the DP-Slave side.
H
E42C
The access was rejected on the DP-Slave side.
H
E42D
Incorrect access range was detected on the DP-Slave side.
H
E42E
Incorrect request was detected on the DP-Slave side.
H
E42F
Incorrect data type was detected on the DP-Slave side.
H
Incorrect parameter in the request was detected on the DP-
E430
H
Slave side.
9
- 16
9.5 Error Codes

9.5.3 Error codes E400H to E4FFH (Error codes generated during acyclic communication)

to E4FF
H
Table9.6 Error codes E400
Error Description
(Error codes generated during acyclic
H
to E4FF
H
H
Check if the specified FDL address is correct, and retry.
Check if the specified read data length is correct, and retry.
Check the detailed error codes 1 to 3 and take corrective
actions.
Check if the specified slot number is correct, and retry.
Check if the specified index is correct, and retry.
Check if the specified CommRef number is correct, and
retry.
Turn ON the Data exchange start request signal (Y00) to
start I/O data exchange.
Verify that the bit corresponding to the DP-Slave is ON in
the Slave status area (Normal communication detection)
(Un\G23040 to Un\G23047) and then retry.
Check the detailed error codes 2 and 3, and take
corrective actions.
Verify that the bit corresponding to the DP-Slave is ON in
the Slave status area (Normal communication detection)
(Un\G23040 to Un\G23047) and then retry.
Check the detailed error codes 2 and 3, and take
corrective actions.
Check the detailed error codes 2 and 3, and take
corrective actions.
Check if the request data supported by the DP-Slave is
correctly set or not, and retry.
For details, refer to the manual for the DP-Slave.
Error codes E400
to E430
H
H
Action
(To the next page)