4 Faults and alarms
4.2 List of faults and alarms
A35222 (F, N)

TM: Encoder pulse number not permissible

Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S, TM15DI_DO, TM31
Reaction:
NONE
Acknowledge:
NONE
Cause:
The encoder pulse number entered does not match the permissible pulse number from a hardware perspective.
Fault value (r0949, interpret decimal):
1: Encoder pulse number is too high.
2: Encoder pulse number is too low.
4: Encoder pulse number is less than the zero mark offset (p4426).
Remedy:
- enter the encoder pulse number in the permissible range (p0408).
- if necessary, replace TM41 SAC with TM41 DAC.
Note:
TM41 SAC: order no. = 6SL3055-0AA00-3PA0
TM41 DAC: order no. = 6SL3055-0AA00-3PA1
The following applies for TM41 SAC:
- minimum/maximum value for p0408: 1000/8192
The following applies for TM41 DAC:
- minimum/maximum value for p0408: 1000/16384
See also: p0408 (Rotary encoder pulse number)
Reaction upon F:
OFF1 (NONE, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A35223 (F, N)

TM: Zero mark offset not permissible

Message value:
%1
Message class:
Application / technological function faulted (17)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S, TM15DI_DO, TM31
Reaction:
NONE
Acknowledge:
NONE
Cause:
The entered zero mark offset is not permissible.
Fault value (r0949, interpret decimal):
1: Zero mark offset is too high.
Remedy:
Enter the zero mark offset in the permissible range (p4426).
Reaction upon F:
OFF1 (NONE, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F35230

TM: Hardware fault

Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S, TM150, TM15DI_DO, TM31
Reaction:
NONE
Acknowledge:
POWER ON
Cause:
The Terminal Module (TM) used has signaled internal errors.
Signals from this module may not be evaluated because they are very likely to be incorrect.
Remedy:
If required, replace the Terminal Module.
1098