Memory Card Not Plugged In; External Fault Triggered; Fuse Monitoring Has Responded - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

A60168 (F, N)

Memory card not plugged in

Message value:
%1
Message class:
General drive fault (19)
Drive object:
DC_CTRL
Reaction:
NONE
Acknowledge:
NONE
Cause:
The data recorded with the recorder function could not be saved on the memory card.
Possible causes:
- Memory card not plugged in
- Memory card defective
Note:
If the save function is performed without errors, the data is saved on the memory card under
"\USER\SINAMICS\DATA\LOG\Tack.csv".
Fault value (r0949, interpret decimal):
1: Unable to create or open the file
2: Unable to write to the file
3: Unable to write all data to the file
See also: p51700 (Signal source for connector recorder function), p51701 (Signal source for binector recorder
function), p51702 (Recorder function channel selection), p51703 (Recorder function recording interval), p51704
(Recorder function save interval), p51705 (Start/stop recorder function)
Remedy:
Plug in a functional memory card (SecureDigital card, SD card).
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F60203 (N, A)

External fault triggered

Message value:
%1
Message class:
General drive fault (19)
Drive object:
DC_CTRL
Reaction:
OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
An external fault has been triggered via terminal 124/125 on the Control Module.
Fault value (r0949, interpret decimal):
Input signal which triggered the fault.
Note:
r50047[1]: External fault mode (p51833)
See also: p51833 (External fault mode)
Remedy:
Eliminate the causes of this fault.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F60204 (N, A)

Fuse monitoring has responded

Message value:
%1
Message class:
General drive fault (19)
Drive object:
DC_CTRL
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
Fuse monitoring on the Control Module has detected at least one blown fuse.
Fault value (r0949, interpret decimal):
1: Monitoring of slot X23B (p51831[0]) has responded.
2: Monitoring of slot X23C (p51831[1]) has responded.
3: Monitoring of slot X23D (p51831[2]) has responded.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
4 Faults and alarms
4.2 List of faults and alarms
1173