Line Frequency Greater Than Maximum Line Frequency; Armature Circuit Uneven Current Distribution - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Remedy:
Check the threshold for monitoring the minimum line frequency (p50363).
See also: p50363 (Line frequency minimum threshold)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F60009 (N, A)

Line frequency greater than maximum line frequency

Message value:
%1
Message class:
Network fault (2)
Drive object:
DC_CTRL
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
The line frequency has overshot the set threshold for monitoring of the maximum line frequency for more than 40 ms.
Fault value (r0949, interpret decimal):
1: Armature supply frequency greater than maximum line frequency
2: Field supply frequency greater than maximum line frequency
Note:
r50047[1]: Incorrect frequency value in Hz
Remedy:
Check the threshold for monitoring the maximum line frequency (p50364).
See also: p50364 (Line frequency maximum threshold)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F60010 (N, A)

Armature circuit uneven current distribution

Message value:
%1
Message class:
Ground fault / inter-phase short-circuit detected (7)
Drive object:
DC_CTRL
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
An uneven current distribution through the thyristors has been identified in the armature circuit.
Significantly less current flows in one thyristor than in the others.
Remarks:
- This monitoring is only effective if the average current value across all thyristors is greater than 20 % of r50072[1].
- The current in a thyristor is significantly lower, if, for a period of one second, the average value is less than 35 % of
the average value across all thyristors.
Possible causes:
- A fuse has blown.
- A thyristor is not fired (defective thyristor, defective pulse transformer, defective firing electronics).
Fault value (r0949, interpret decimal):
Number of the thyristor that is conducting the significantly lower current.
Note:
r50047[1]: Average current value through all armature thyristors.
r50047[2]: Average current value through the thyristor with the excessively low current, in torque direction I.
r50047[3]: Average current value through the thyristor with the excessively low current, in torque direction II.
The current values as a % are referred to r50072[1].
Note:
Even though the response to this fault message is set to "NO" when using p2100/p2101, or the message type set to
"Alarm" or "No message" when using p2118/p2119, in the case of a fault, the drive still exits the OPERATION (RUN)
state and goes into state o4.1 (wait for the fuse monitoring OK message.)
Remedy:
- Check the fuses in the power unit.
- If required, perform a thyristor diagnostics routine (p50830).
See also: p50830 (Thyristor diagnostics mode)
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
4 Faults and alarms
4.2 List of faults and alarms
1141