Advertisement

4 Faults and alarms
4.2 List of faults and alarms
4: Monitoring of slot X23E (p51831[3]) has responded.
5: Monitoring of slot X23F (p51831[4]) has responded.
Note:
r50047[1]: Fuse number (XS1, XS2 to XS6)
See also: p51831 (Fuse monitoring activation)
Remedy:
- Analyze the blown fuse.
- Replace or close fuses as necessary.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A60266 (F, N)

Alarm fan not OK

Message value:
%1
Message class:
Overtemperature of the electronic components (6)
Drive object:
DC_CTRL
Reaction:
NONE
Acknowledge:
NONE
Cause:
For a control module without option Z01... Z15, the following applies:
The signal at terminal 122/123 signals "Fan not OK".
The fan might be blocked or faulty.
Alarm value (r2124, interpret decimal):
Alarm value 1: Signal at terminal 122/123 signals "Fan not OK".
r50047[1]: Fan monitoring mode (p51832)
For a control module with option Z01... Z15, the following applies:
The alarm threshold for the differential pressure was fallen below.
Alarm value 2: differential pressure at LT1 fallen below
Alarm value 3: differential pressure at LT2 fallen below
r50047[1]: Fan monitoring mode (p51832)
Remedy:
- Check wiring of "Fan OK" message via input terminal 122/123.
- Check the setting of the mode for fan monitoring (p51832).
- Check the fan and replace if necessary.
See also: p51832 (Fan monitoring configuration), p51835 (Delay times for device fan monitoring)
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F60267 (N, A)

CM: Fan not OK

Message value:
%1
Message class:
Overtemperature of the electronic components (6)
Drive object:
DC_CTRL
Reaction:
OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
For a control module without option Z01... Z15, the following applies:
The signal at terminal 122/123 signals "Fan not OK".
The fan might be blocked or faulty.
Alarm value (r2124, interpret decimal):
Alarm value 1: Signal at terminal 122/123 signals "Fan not OK".
r50047[1]: Fan monitoring mode (p51832)
1174
List Manual (LH8), 02/2015, 6RX1800-0ED76
SINAMICS DCM