Error Transferring The Data Record Dq - Siemens SIMATIC ET 200SP Manual

Digital output module dq 4x24..230vac/2a hf 6es7132-6fd00-0cu0
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

A.2

Error transferring the data record DQ

Error transferring the data record
The module always checks all the values of the transferred data record. Only if all the values
were transferred without errors does the module apply the values from the data record.
The WRREC instruction for writing data records returns corresponding error codes when
errors occur in the STATUS parameter. (See also the description of the "STATUS"
parameter in the STEP 7 online help).
The following table shows the module-specific error codes and their meaning for the
parameter data record 128.
Error code in STATUS parameter
(hexadecimal)
Byte 0
Byte 1
Byte 2
DF
80
B0
DF
80
B1
DF
80
B2
DF
80
E0
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DQ 4x24..230VAC/2A HF digital output module (6ES7132-6FD00-0CU0)
Manual, 02/2018, A5E42404845-AA
Meaning
Byte 3
xx
Number of the data record un-
known.
xx
Length of the data record incorrect. Enter a valid value for the data record length.
xx
Slot invalid or cannot be accessed. •
xx
Wrong version or error in the
header information.
01
At least one reserved bit is set to
"1".
02
Overflow diagnostics is enabled
even though DQ mode is active.
05
Invalid coding for operating mode.
06
Invalid coding for substitute value
behavior.
20
Invalid coding for startup delay.
21
Invalid coding for output filter up or
down.
Parameter data record
A.2 Error transferring the data record DQ
Solution
Enter a valid number for the data record.
Check the station whether the module is
plugged or drawn.
Check the assigned values for the pa-
rameters of the WRREC instruction.
Correct the version, length and number of
parameter blocks.
Set all reserved bits to "0".
Block all Overflow diagnostics or switch to PC
mode.
Check module parameters.
Check all channel parameters.
Check all channel parameters.
Check all channel parameters.
55