Technical Data - Siemens FN2013-U1 Installation Manual

Fiber network module
Table of Contents

Advertisement

1
Fiber network module FN2013 / FN2014

Technical data

LED
Color
RX2
Green
Power B
Green
Power A
Green
LNK1
Green
EF1
Yellow
EF2
Yellow
LNK2
Green
1.6 Technical data
Supply input
Supervision contact
Fibre optic cable
FN2014-U1
18 | 28
Function
Receiving data from fiber-
optic circuit '2'
Supervision of feeding voltage
for 'Power B'
Supervision of feeding voltage
for 'Power A'
Data transmission HNET/
XNET/HUB-4/SNC - circuit '1'
Data transmission HNET/
XNET/HUB-4/SNC - circuit '2'
Input voltage
Decentralized mounting
Operating current
Do not use
Type of connection
Cable end box
Wavelength
Multi-mode
Range:
Fiber type 62.5/125 µm
Fiber type 50/125 µm
Optical budget:
Fiber type 62.5/125 µm
Fiber type 50/125 µm
2023-01-23
Condition Meaning
Lit up
Data is being received from circuit '2'
On
Normal operation (feeding voltage
available)
Off
No feeding voltage or voltage below
minimum input voltage (9 V)
On
Normal operation (feeding voltage
available)
Off
No feeding voltage or voltage below
minimum input voltage (9 V)
Flashes
Data is being transmitted via A1/B1
Off
Not used
Off
Not used
Flashes
Data is being transmitted via A2/B2
DC 24 V
Shielded supply cable (not in scope of
supply)
Max. 132 mA @ DC 24 V
-
SC connector
Standard 'PC' or 8° polish 'APC'
1310 nm (for MM and SM)
13100 ft/4000 m
6550 ft/2000 m
11 dBm
7.5 dBm
A6V12093642_en--_b