4 Faults and alarms
4.2 List of faults and alarms
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F60012 (N, A)

P2P-IF: Telegram monitoring time expired

Message value:
-
Message class:
Communication error to the higher-level control system (9)
Drive object:
DC_CTRL
Reaction:
OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The telegram monitoring time for communication via the peer-to-peer interface (P2P-IF) has expired.
No further valid telegrams were received during the monitoring time (p50797).
Possible causes:
- Break in connecting cable
- Electromagnetic interference on the connecting cable
- Telegram monitoring time set too short (p50797)
Remedy:
- Check connecting cable and cable connection.
- Check that the connecting cable has been routed in compliance with EMC.
- Increase the telegram monitoring time if necessary (p50797).
See also: p50089 (Sequence control voltage at power unit wait time), p50790 (P2P IF operating mode), p50797 (P2P
IF telegram monitoring time)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F60014 (N, A)

Parallel interface telegram monitoring time expired

Message value:
-
Message class:
Communication error to the higher-level control system (9)
Drive object:
DC_CTRL
Reaction:
OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The telegram monitoring time for communication via the parallel interface (Par-IF) has expired.
No further valid telegrams were received during the monitoring time (p51807).
Possible causes:
- Break in connecting cable
- Electromagnetic interference on the connecting cable
- Telegram monitoring time set too short (p51807)
Remedy:
- Check connecting cable and cable connection.
- Check that the connecting cable has been routed in compliance with EMC.
- Increase the telegram monitoring time if necessary (p51807).
See also: p51807 (Parallel interface telegram monitoring failure time), p51808 (Parallel interface signal source for
F60014)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A60018 (F, N)

Digital output overloaded

Message value:
Fault cause: %1 bin
Message class:
Ground fault / inter-phase short-circuit detected (7)
Drive object:
DC_CTRL
Reaction:
NONE
Acknowledge:
NONE
Cause:
At least one digital output is overloaded or has short-circuited.
1142
List Manual (LH8), 02/2015, 6RX1800-0ED76