Tm: Error Temperature Sensor Channel 11; Tm: Unknown Alarm; Hub Drive-Cliq: Error Below The Signaling Threshold - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

4 Faults and alarms
4.2 List of faults and alarms
A35931 (F, N)

TM: Error temperature sensor channel 11

Message value:
%1
Message class:
External measured value / signal state outside the permissible range (16)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S, TM150
Reaction:
NONE
Acknowledge:
NONE
Cause:
When evaluating the temperature sensor, an error occurred.
Alarm value (r2124, interpret decimal):
1: Wire breakage or sensor not connected.
KTY84: R > 2170 Ohm, PT100: R > 194 Ohm, PT1000: R > 1944 Ohm
2: Measured resistance too low.
PTC thermistor: R < 20 Ohm, KTY84: R < 180 Ohm, PT100: R < 60 Ohm, PT1000: R < 603 Ohm
Remedy:
- make sure that the sensor is connected correctly.
- replace the sensor.
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A35999 (F, N)

TM: Unknown alarm

Message value:
New message: %1
Message class:
General drive fault (19)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S, TM150, TM15DI_DO, TM31
Reaction:
NONE
Acknowledge:
NONE
Cause:
An alarm has occurred on the Terminal Module that cannot be interpreted by the Control Unit firmware.
This can occur if the firmware on this component is more recent than the firmware on the Control Unit.
Alarm value (r2124, interpret decimal):
Alarm number.
Note:
If required, the significance of this new alarm can be read about in a more recent description of the Control Unit.
Remedy:
- replace the firmware on the Terminal Module by an older firmware version (r0158).
- upgrade the firmware on the Control Unit (r0018).
Reaction upon F:
NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A36840

Hub DRIVE-CLiQ: error below the signaling threshold

Message value:
Component number: %1, fault cause: %2
Message class:
Internal (DRIVE-CLiQ) communication error (12)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
NONE
Acknowledge:
NONE
Cause:
A DRIVE-CLiQ error has occurred below the signaling threshold.
Fault cause:
1 (= 01 hex):
Checksum error (CRC error).
2 (= 02 hex):
Telegram is shorter than specified in the length byte or in the receive list.
3 (= 03 hex):
Telegram is longer than specified in the length byte or in the receive list.
4 (= 04 hex):
The length of the receive telegram does not match the receive list.
1122
List Manual (LH8), 02/2015, 6RX1800-0ED76
SINAMICS DCM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents