Encoder 2: Effectivity Test Does Not Supply The Expected Value; Encoder 2: Group Signal; Encoder 2 Drive-Cliq: Sign-Of-Life Missing; Encoder 2: Time Slice Overflow - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Reaction upon A:
NONE
Acknowl. upon A:
NONE
A32700

Encoder 2: Effectivity test does not supply the expected value

Message value:
Fault cause: %1 bin
Message class:
Safety monitoring channel has identified an error (10)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
NONE
Acknowledge:
NONE
Cause:
The DRIVE-CLiQ encoder fault word supplies fault bits that have been set.
Fault value (r0949, interpret binary):
Bit x = 1: Effectivity test x unsuccessful.
Remedy:
Replace encoder.
N32800 (F)

Encoder 2: Group signal

Message value:
-
Message class:
Position/speed actual value incorrect or not available (11)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
OFF1 (IASC/DCBRK, NONE, OFF2, OFF3)
Acknowledge:
NONE
Cause:
The motor encoder has detected at least one fault.
Remedy:
Evaluates other actual messages.
Reaction upon F:
OFF1 (IASC/DCBRK, NONE, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
F32801 (N, A)

Encoder 2 DRIVE-CLiQ: Sign-of-life missing

Message value:
Component number: %1, fault cause: %2
Message class:
Internal (DRIVE-CLiQ) communication error (12)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
OFF1 (IASC/DCBRK, NONE, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communication error has occurred from the Control Unit to the encoder involved.
Fault cause:
10 (= 0A hex):
The sign-of-life bit in the receive telegram is not set.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- check the electrical cabinet design and cable routing for EMC compliance
- replace the component involved.
See also: p9916 (DRIVE-CLiQ data transfer error shutdown threshold slave)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F32802 (N, A)

Encoder 2: Time slice overflow

Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
OFF1 (IASC/DCBRK, NONE, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
A time slice overflow has occurred in encoder 2.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
4 Faults and alarms
4.2 List of faults and alarms
1067

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents