F60104 (N, A)

Armature circuit line voltage not OK

Message value:
%1
Message class:
Network fault (2)
Drive object:
DC_CTRL
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
On power-up, the time set in p50089 represents the maximum wait time for voltage at the power connections and for
field current in operating states o5 and o4 combined.
On power-up, the time set in p50095 represents the maximum wait time for "Line contactor feedback" in operating
state o3.3 (if activated, see p50691).
This fault is triggered if the above times elapse in one of these operating states.
- Thresholds for the line monitoring incorrectly set (p50078, p50351, p50352, p50353, p50363, p50364).
- Armature voltage not OK (phase failure, undervoltage/overvoltage, underfrequency/overfrequency).
- Line contactor not picking up
- Fuse blown on three-phase side of armature circuit
- Fuse blown in power unit
- Interruption affecting thyristor firing pulse cable (auxiliary cathodes at connections X12, X14, X16 are used for
voltage transmission).
Fault value (r0949, interpret decimal):
2: Wait time set in p50089 has expired in operating state o4.0.
3: Fuse blown on three-phase side of armature circuit
6: Wait time set in p50095 has expired in operating state o3.3.
Note for fault value = 2:
- r50047[1]: line state (r53145)
Bit 0 = 1: Armature supply line, overvoltage
Bit 1 = 1: Armature supply line, undervoltage
Bit 2 = 1: Armature supply line, overfrequency
Bit 3 = 1: Armature supply line, underfrequency
Bit 4 = 1: Armature supply line, phase failure
Bit 5 = 1: Field supply line, overvoltage
Bit 6 = 1: Field supply line, undervoltage
Bit 7 = 1: Field supply line, overfrequency
Bit 8 = 1: Field supply line, underfrequency
Bit 9 = 1: Field supply line, phase failure
Bit 10 = 1: Armature supply line OK
Bit 11 = 1: Field supply line OK
Bit 12 = 1: clockwise phase sequence
Bit 13 = 1: Line symmetrical
See also: p50089 (Sequence control voltage at power unit wait time), p50095 (Sequence control DC circuit contactor
wait time), p50691 (Sequence control line contactor feedback)
Remedy:
- Check the thresholds for the line monitoring (p50078, p50351, p50352, p50353, p50363, p50364).
- Check line voltage and line contactor.
- Check fuses for armature circuit.
- Check thyristor firing pulse cable (X12, X14, X16).
See also: p50089 (Sequence control voltage at power unit wait time), p50353 (Line monitoring phase failure
threshold)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
4 Faults and alarms
4.2 List of faults and alarms
1169