PTX5000 Packet Transport Router Hardware Guide
218
Figure 115: Connecting Power to a Three-Phase Wye AC PDU
Connect the wires to the AC terminal block on the three-phase wye AC power supply
7.
(Figure 116 on page
219). Using a 1/5-in. (5.5-mm) slotted screwdriver, loosen each of
the input terminals or grounding point screws, insert each wire into the grounding
point or input terminal, and tighten the screw.
Insert the wire labeled
a.
Insert the wire labeled
b.
Insert the wire labeled
c.
Insert the wire labeled
d.
Insert the wire labeled
e.
CAUTION:
wire to the
into the grounding point.
GND
into the
input terminal.
L1
L1
into the
input terminal.
L2
L2
into the
input terminal.
L3
L3
into the
input terminal
N
N
To avoid damage to the PDU, do not connect the neutral
L1
,
L2
, or
L3
input terminals.
Copyright © 2017, Juniper Networks, Inc.