PTX5000 Packet Transport Router Hardware Guide
PTX5000 DC Power Distribution Unit Specifications
140
PTX5000 DC Power Distribution Unit Specifications on page 140
Calculating PTX5000 Power Consumption on page 123
PTX5000 DC Power Cable and Lugs Specifications on page 141
PTX5000 DC Power Distribution on page 143
Table 64 on page
140,
Table 65 on page
specifications for each DC power distribution unit (PDU).
For circuit breaker requirement, see
Circuit Breaker Specifications" on page 114
Table 64: 60-A DC PDU Electrical Specifications
Item
DC input voltage
Input DC current rating
Table 65: 120-A PDU Electrical Specifications
Item
DC input voltage
Input DC current rating
Table 66: High Capacity PDU Electrical Specifications
Item
DC input voltage
Input DC current rating
To allow for future growth so that you can operate the PTX5000 in any hardware
configuration without upgrading the power infrastructure, we recommend that you
provision the following:
60-A DC PDU: 51 A @ –48 VDC per input.
120-A DC PDU: 92.5 A @ –48 VDC per input.
140, and
Table 66 on page 140
"PTX5000 AC and DC PDU Electrical and External
or as required by local code.
Specification
Nominal –48 VDC, –60 VDC
Operating range: –40.0 to –72.0 VDC
51 A @ –48 VDC (nominal) (2444 W) per input
Specification
Nominal –48 VDC, –60 VDC
Operating range: –40.0 to –72.0 VDC
92.5 A @ –48 VDC (nominal) (4440 W) per
input
Specification
Nominal –48 VDC, –60 VDC
Operating range: –40.0 to –72.0 VDC
44.2 A @ –48 VDC (nominal) (2120 W) per
input
Copyright © 2017, Juniper Networks, Inc.
list the electrical