PTX5000 Packet Transport Router Hardware Guide
332
Connect the wires to the AC terminal block on the three-phase wye AC PDU
10.
(Figure 207 on page
332). Using a 1/5-in. (5.5-mm) slotted screwdriver, loosen the
input terminal or grounding point screw, and insert each wire into the grounding point
or input terminal, and tighten the screw.
Insert the wire labeled
a.
Insert the wire labeled
b.
Insert the wire labeled
c.
Insert the wire labeled
d.
Insert the wire labeled
e.
Figure 207: Connecting Grounding and AC Power Wires to a Three-Phase
Wye AC PDU
Verify that the AC power and grounding wire connections are correct.
11.
Using a number 2 Phillips (+) screwdriver, tighten the two captive screws on the metal
12.
AC wiring compartment.
Verify that the AC power cord is not touching or blocking access to chassis components,
13.
and that it does not drape where people could trip on it.
Reconnect the AC power cord to the power source.
14.
GND
into the grounding point.
L1
into the
L1
input terminal.
L2
into the
L2
input terminal.
L3
into the
L3
input terminal.
N
into the
N
input terminal.