Table 49: Ptx5000 Ac Pdu Electrical And External Circuit Breaker; Table 50: Ptx5000 Dc Pdu Electrical And External Circuit Breaker - Juniper PTX5000 Hardware Manual

Packet transport router
Hide thumbs Also See for PTX5000:
Table of Contents

Advertisement

PTX5000 Packet Transport Router Hardware Guide
PTX5000 AC and DC PDU Electrical and External Circuit Breaker Specifications
Table 49: PTX5000 AC PDU Electrical and External Circuit Breaker Specifications
PDU
Normal Capacity Three-phase AC
Delta PDU (PDU-PTX-AC-D)
Normal Capacity Three-phase AC
Wye PDU (PDU-PTX-AC-W)
High Capacity Delta AC PDU
(PDU2-PTX-AC-D) with 60 A power
cord
High Capacity Delta AC PDU
(PDU2-PTX-AC-D) with 100 A
power cord
High Capacity Delta AC PDU
(PDU2-PTX-AC-D) with 150 A power
cord
High Capacity Wye AC PDU
(PDU2-PTX-AC-W)
Table 50: PTX5000 DC PDU Electrical and External Circuit Breaker Specifications
PDU
Normal Capacity 60-A DC
PDU (PDU-PTX-DC-60)
Normal Capacity 120-A DC
PDU (PDU-PTX-DC-120)
High Capacity DC PDU
(PDU2-PTX-DC)
114
Connecting the PTX5000 Grounding Cable on page 185
Table 49 on page 114
lists the AC PDU electrical and external circuit breaker specifications.
Maximum
Cable
Current
Amp
Drawn
Rating
48 A
60 A
32 A
32 A
48 A
60 A
80 A
80 A
114 A
120 A
56 A
63 A
Table 50 on page 114
lists the DC PDU electrical and external circuit breaker specifications.
Maximum
Cable
Current
Amp
Drawn
Rating
48 A
NA
93 A
NA
48 A
NA
External
Circuit
Operational
Breaker/Fuse
Voltage
60 A
200 V–240 V
32 A
200 V–240 V
60 A
200 V–240 V
80 A
200 V–240 V
120 A
200 V–240 V
63 A
200 V–240 V
External Circuit
Operational
Breaker/Fuse
Voltage
48 A–60 A
48 V–60 V
93 A–120 A
48 V–60 V
48 A–60 A
48 V–60 V
Copyright © 2017, Juniper Networks, Inc.
Feeds
per
Plug
PDU
Rating
1
60 A
1
32 A
1
60 A
1
100 A
1
150 A
1
63 A
Feeds
Plug
per PDU
Rating
8
NA
4
NA
16
NA

Advertisement

Table of Contents
loading

Table of Contents