Figure 134: Connecting Power To A High Capacity Wye Ac Pdu - Juniper PTX5000 Hardware Manual

Packet transport router
Hide thumbs Also See for PTX5000:
Table of Contents

Advertisement

PTX5000 Packet Transport Router Hardware Guide
234
Attach the power cord to the PDU:
7.
Using a number 2 Phillips (+) screwdriver, loosen the two captive screws on the
a.
metal AC wiring compartment.
Open the metal door of the metal AC wiring compartment.
b.
Push the wires of the AC power cord into the area for the metal retaining bracket,
c.
and pull the wires to the left toward the metal AC wiring compartment.
Using a number 2 Phillips (+) screwdriver, use the four captive screws on the metal
d.
retaining bracket to secure the AC power cord to the PDU (see
Figure 134 on page
234).

Figure 134: Connecting Power to a High Capacity Wye AC PDU

Connect the wires to the AC terminal block on the High Capacity Wye AC PDU (see
8.
Figure 135 on page
234). Using a 1/5-in. (5.5-mm) slotted screwdriver, loosen each of
the input terminal screws and the grounding point screw, insert each wire into the
grounding point or input terminal, and tighten the screw.
Insert the neutral wire labeled
a.
Insert the wire labeled
b.
Insert the wire labeled
c.
Insert the wire labeled
d.
Insert the wire labeled
e.
CAUTION:
wire to the
into the grounding point.
GND
into the
input terminal.
L1
L1
into the
input terminal.
L2
L2
into the
input terminal.
L3
L3
into the
input terminal.
N
N
To avoid damage to the PDU, do not connect the neutral
,
, or
input terminal.
L1
L2
L3
Copyright © 2017, Juniper Networks, Inc.