Using a number 2 Phillips (+) screwdriver, loosen the two captive screws to the metal
7.
wiring compartment door. Open the door of the metal wiring compartment. Disconnect
the wires from the AC terminal block on the High Capacity Wye AC PDU
(Figure 224 on page
353). Using 7/32-in. (5.5-mm) slotted screwdriver, loosen the input
terminal screws and the grounding point screw, and remove each wire from the input
terminal points and the grounding point.
Remove the wire labeled
a.
Remove the wire labeled
b.
Remove the wire labeled
c.
Remove the wire labeled
d.

Figure 224: Disconnecting AC Power Wires from a High Capacity Wye AC

PDU
Using a number 2 Phillips (+) screwdriver, loosen the screws that secure the metal
8.
retaining bracket and AC power cord to the PDU. While gently removing the wires of
the AC power cord from the wiring compartment, remove the metal retaining bracket
and AC power cord from the PDU. See
Chapter 27: Removing and Installing Power System Components
L3
from the
L3
input terminal.
L2
from the
L2
input terminal.
L1
from the
L1
input terminal.
GND
into the grounding point.
Figure 225 on page
354.
353