Verify that the AC power wiring connections are correct.
8.
Close the door to the metal AC wiring compartment, and use a number 2 Phillips (+)
9.
screwdriver to tighten the two captive screws to secure the door to the metal AC
wiring compartment.
Verify that the AC power cord does not touch or block access to PTX5000 components,
10.
and that it does not drape where people could trip on it.
Before you power on the PDU, select the switch setting corresponding to the AC input
11.
power cord that is connected to the PDU.
switch, located inside the wiring compartment.
If CBL-PTX-AC-D cable is used, set the switch to 60A.
If CBL2-PTX-100AC-D cable is used, set the switch to 100A.
If CBL2-PTX-150AC-D cable is used, set the switch to 150A.
You can verify the switch setting by using the
The command displays the input power rating as shown in the following example:
show chassis environment pdu 0
PDU 0 status:
State Online
BoostConv OK
Feed Switch 150Amps <<<===
Hours Used 142
Chapter 21: Connecting the Router to Power
Figure 128 on page 230
shows an ampere
show chassis environment pdu
command.
229