PTX5000 Packet Transport Router Hardware Guide
214
Connect the wires to the AC terminal block on the three-phase delta AC PDU
7.
(Figure 109 on page
214). Using a 1/5-in. (5.5-mm) slotted screwdriver, loosen each of
the input terminals or grounding point screws, insert each wire into the grounding
point or input terminal, and tighten the screw.
Insert the wire labeled
a.
Insert the wire labeled
b.
Insert the wire labeled
c.
Insert the wire labeled
d.
Figure 109: Connecting Ground and Power to a Three-Phase Delta AC
PDU
Verify that the AC power wiring connections are correct.
8.
Close the door to the metal AC wiring compartment, and use a number 2 Phillips (+)
9.
screwdriver to tighten the two captive screws to secure the door to the metal AC
wiring compartment.
Verify that the AC power cord does not touch or block access to PTX5000 components,
10.
and that it does not drape where people could trip on it.
Repeat the procedure for the other three-phase delta AC PDU.
11.
GND
into the grounding point.
L1
into the
L1
input terminal.
L2
into the
L2
input terminal.
L3
into the
L3
input terminal.
Copyright © 2017, Juniper Networks, Inc.