(F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
5.8.7

Lift operation (automatic acceleration/deceleration)

The inverter can be operated according to the load pattern of the lift with counterweight.
Pr.
292
F500
61
F510
64
F520
The setting range for the FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower.
The setting range for the FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher.
Lift operation (Pr. 292 = "5, 6")
● When Pr. 292 "Automatic acceleration/deceleration" is set to "5" or "6", the lift operation is selected,
and each setting is changed, as shown in the table below.
● During power driving, sufficient torque is generated, and during regenerative driving and during
driving with no load, the torque boost setting is adjusted automatically so as not to activate the
overcurrent protective function by overexcitation.
Name
Torque boost
Starting frequency
Base frequency voltage
Stall prevention operation level
Tab. 5-100: Valid values in the elevator mode
5 - 268
Initial
Name
Automatic acceleration/
deceleration
Reference current
Starting frequency for
elevator mode
Normal operation
Pr. 0 (6/4/3/2/1%)
Pr. 13 (0.5 Hz)
Pr. 19 (9999)
Pr. 22 (150%), etc.
Setting range
value
0
1
11
3
0
5
6
7, 8
0 to 500 A
0 to 3600 A
9999
9999
0 to 10 Hz
9999
9999
Multi-
rating
(Pr. 570)
0(SLD)
1(LD)
2(ND)
Initial value
3(HD)
V/F
V/F
V/F
Description
Normal operation
Shortest acceleration/
deceleration (without brakes)
Shortest acceleration/
deceleration (with brakes)
Optimum acceleration/
deceleration
Lift operation 1 (stall prevention operation
level 150%)
Lift operation 2 (stall prevention operation
level 180%)
Brake sequence 1, 2
(Refer to page 5-501.)
Set the reference current during shortest
(optimum) acceleration/deceleration.
Rated output current value reference of the
inverter
Set the starting frequency for the lift
operation.
Starting frequency is 2 Hz.
Lift operation (Pr. 292)
5
Changes according to the output current
(as shown below)
Pr. 64 (2 Hz) Accelerate after 100 ms hold.
220 V (440 V )
110%
120%
150%
200%
Parameters
(Refer to
page 5-263.)
6
115%
140%
180%
230%