Clean- 3.2.2 Low Flow Pump Pressure/Isolate Valve #43 - Fresenius Medical Care 2008K2 Troubleshooting Manual

Hemodialysis system
Hide thumbs Also See for 2008K2:
Table of Contents

Advertisement

Yes
Between 34 and 36 psi! Proceed to
No Remains less than 34 psi! ENSURING Heat Disinfect OR Rinse is running AND no leaks, see
parts a THROUGH c below:
a) Watch for one (1) minute to ENSURE a "No Water" alarm NEVER occurs!
b) Referring to
c) Can you adjust Valve #78 until the gauge cycles to a PEAK of between 34 and 36 psi?
Yes
No Pressure DOES NOT adjust. TWO (2) possible scenarios:
CLEAN- 3.2.2 LOW FLOW PUMP PRESSURE / ISOLATE VALVE #43
Per the Figures below
a)
output tubing extends towards the front of the machine!
b) Can you now adjust Valve #78 until gauge pressure cycles to between 34 psi and 36 psi about every
three (3) seconds (Yes of No)?
Yes
Between 34 and 36 psi! This may indicate Valve #43 sticking open! A) Release the clamps!
B) ENSURING Valve #43's 'dot' is white, if pressure again DOES NOT cycle to more than
34 psi then TWO (2) possible bad components: 1) Bad Actuator-Test Board OR; 2) Bad
Valve #43.
No
Remains less than 34 psi! Leaving the clamps in place, proceed to
number
F-
Figure 32
(page 158), behind the Deair Pump, locate
Pressure between 34 and 36 psi! Allow two (2) minutes then, if a Flow Error
reoccurs, proceed to
1)
IF (and ONLY if) pressure remains low: See procedure number
CLEAN- 3.2.2
2) IF pressure remains high: Valve #78 may be bad!
, DOUBLE clamp the OUTPUT tubing at Valve #43.
9.0.24.
2008K/K2 Troubleshooting Guide
P/N 507298 Rev. H
page 175
, procedure number
page 175
, procedure number
(page 174).
CLEAN-
4.0.0.
Valve #78
.
CLEAN-
4.0.0.
NOTE:
Valve #43's
page 94
procedure
Page 174

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

2008k

Table of Contents