Acceleration Pre-Control - BONFIGLIOLI Agile Operating Instructions Manual

Frequency inverter 230 v / 400 0.09 kw ... 11 kw
Hide thumbs Also See for Agile:
Table of Contents

Advertisement

7.9.5.3.2 Limit value sources
734 Isq Limit Source Motor Operation
735 Isq Limit Source Generator Op.
736 Torque Limit Source Motor Op.
737 Torque Limit Source Gen. Op.
As an alternative to limiting the output values by a fixed value, linking to an analog input value is also
possible. The analog value is limited via parameters
519, but does not consider the
Reference Percentage
ence percentage value channel.
The assignment is done with the help of the parameters
Isq Limit Source Generator Op.
The sources for the torque limits can be selected via the parameters
736 and
Torque Limit Source Gen. Op.
Operation mode
734, 735, 736, 737
101 - Analog Input MFI1A
102 - Analog Input MFI2A
Repetition Percentage
105 -
Input
110 - Fixed Limit
714 - RxPDO2 Word 1
715 - RxPDO2 Word 2
PLC Output Percent-
2521 -
age 1
PLC Output Percent-
2522 -
age 2
The limit values and assignment to different limit value sources are data set related in
the configurations. The use of the data record changeover demands an examination of
the parameters in question.
7.9.5.3.3 Switching over between speed control and torque control
Via the signal assigned to parameter
control and torque control. See chapter 7.6.6.10 "n-/T-control changeover".
7.9.5.4

Acceleration pre-control

725 Operation Mode
The acceleration pre-control controlled parallel to the speed controller reduces the reaction time of the
drive system to a change of reference values.
The acceleration pre-control is active in the speed-controlled configurations and can be activated via
parameter
Operation Mode
725
Operation Mode
0 - Off
1 - Switched on
Agile
Operating Instructions
735 for the torque-forming current component Isq.
737.
Multifunction input 1 is the source. Via parameter
452, multifunction input 1 must be set up as a voltage or
MFI1
current input.
Multifunction input 2 is the source. Via parameter
562, multifunction input 2 must be set up as a voltage or
MFI2
current input.
The percentage signal at the repetition frequency input (IN2D, ter-
minal X11.5).
Operation Mode IN2D
See chapter 7.6.7 "Input PWM/repetition frequency/pulse train".
The selected parameter figures for limiting the speed controller are
taken into account. Factory setting.
Process data of the system bus. Refer to instructions on system bus.
Process data of the system bus. Refer to instructions on system bus.
Output value of a PLC-function. Refer to application manual "PLC".
Output value of a PLC-function. Refer to application manual "PLC".
n-/T-Control Change-Over
725.
The control system is not influenced. Factory setting.
The acceleration pre-control is active according to the limit values.
236
06/2013
Minimum Reference Percentage
Gradient Percentage Ramp
Isq Limit Source Motor Operation
Torque Limit Source Motor Op.
Function
496 must be set to 20 or 21.
164, you can switch between speed
Function
Parameter descriptions
518,
Maximum
477 of the refer-
734 and
Operation Mode
Operation Mode
Control functions