Operation Mode Motor
570
Temp.
0 - Off
Therm.-Contact, P204:
1 -
Warning only
Therm.-Contact, P204:
2 -
Error Switch-Off
Therm.-Contact, P204:
3 -
Err.Switch-Off 1 min
delayed
MPTC, MFI2: Warning
11 -
only
MPTC, MFI2: Error
12 -
Switch-Off
MPTC, MFI2: Err.Switch-
13 -
Off 1 min delayed
21 - KTY, MFI2: Warning only
Agile
Operating Instructions
Motor temperature monitoring switched off.
Monitoring for temperature limit. A thermal overload is displayed via
the operator panel and parameter
Thermal contact for P570
mal contact is connected must be selected. In the factory setup,
multifunction input 2 can be used for connection of a thermal con-
tact (
Thermal contact for P570
signal must be digital. The evaluation (NPN/PNP) of the input signal
can be set via parameter
Monitoring for temperature limit. The frequency inverter is switched
off immediately if the motor is thermally overloaded. The error
switch-off is displayed by message F0400. For parameter
204, the digital input to which the thermal contact
contact for P570
is connected must be selected. In the factory setup, multifunction
input 2 can be used for connection of a thermal contact (
204 is set to MFI2D). The input signal must be
contact for P570
digital. The evaluation (NPN/PNP) of the input signal can be set via
parameter
Operation mode MFI2
Monitoring for temperature limit. The frequency inverter is switched
off if the motor is thermally overloaded. The error switch-off is dis-
played by message F0400. The error switch-off is delayed by one
minute. For parameter
Thermal contact for P570
input to which the thermal contact is connected must be selected. In
the factory setup, multifunction input 2 can be used for connection
of a thermal contact (
Thermal contact for P570
MFI2D). The input signal must be digital. The evaluation (NPN/PNP)
of the input signal can be set via parameter
562.
Monitoring for temperature limit. A thermal overload is displayed via
the operator panel and parameter
input 2 can be used as input for monitoring of a temperature value
with motor PTC (PTC as per DIN 44081). The input signal must be
analog.
Monitoring for temperature limit. The frequency inverter is switched
off immediately if the motor is thermally overloaded. The error
switch-off is displayed by message F0400. Multifunction input 2 can
be used as input for monitoring of a temperature value with motor
PTC (PTC as per DIN 44081). The input signal must be analog.
Monitoring for temperature limit. The frequency inverter is switched
off if the motor is thermally overloaded. The error switch-off is dis-
played by message F0400. The error switch-off is delayed by one
minute. Multifunction input 2 can be used as input for monitoring of
a temperature value with motor PTC (PTC as per DIN 44081). The
input signal must be analog.
Temperature measurement. A thermal overload is displayed via the
operator panel and parameter
played as soon as the value of
reached. Multifunction input 2 can be reached as input for tempera-
ture measurement with a KTY measuring resistor (KTY84). The in-
put signal must be analog. Parameter
shows the actual value.
138
06/2013
Parameter descriptions
Function
269. For parameter
Warnings
204, the digital input to which the ther-
204 is set to MFI2D). The input
562.
Operation mode MFI2
562.
204, the digital
204 is set to
Operation mode MFI2
269. Multifunction
Warnings
269. The warning is dis-
Warnings
Max. Temp. Motor Winding
Winding temperature
Error and warning behavior
Thermal
Thermal
617 is
226

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents