Parameter descriptions
Operation Mode Motor
570
Temp.
KTY, MFI2: Error Switch-
22 -
Off
KTY, MFI2: Err.Switch-
23 -
Off 1 min delayed
PT1000, MFI2: Warning
31 -
only
PT1000, MFI2: Error
32 -
Switch-Off
PT1000, MFI2:
33 -
Err.Switch-Off 1 min
delayed
Error Acknowledgment
− Thermal contact or MPTC: An error message can be acknowledged if the sensor does not signal
overtemperature anymore.
− KTY or PT1000: An error message can be acknowledged if the motor temperature has dropped
below the switch-off threshold by 5°C.
Possibilities of error acknowledgement:
− via operator panel or
− via parameter
Error Acknowledgement
Evaluation of the motor temperature is independent of the controller enable.
If motor temperature monitoring with MPTC, KTY or PT1000 is selected via parameter
Operation Mode Motor Temp.
functions. In this case, parameters 560 ... 567 of multifunction input 2 don't have any
function.
Error and warning behavior
Temperature measurement. The frequency inverter is switched off
immediately as soon as the value of
617 is reached. The error switch-off is displayed by message F0400.
Multifunction input 2 can be reached as input for temperature
measurement with a KTY measuring resistor (KTY84). The input
signal must be analog. Parameter
the actual value.
Temperature measurement. The frequency inverter is switched off
as soon as the value of
Max. Temp. Motor Winding
The error switch-off is displayed by message F0400. The error
switch-off is delayed by one minute. Multifunction input 2 can be
reached as input for temperature measurement with a KTY measur-
ing resistor (KTY84). The input signal must be analog. Parameter
226 shows the actual value.
Winding Temperature
Temperature measurement. A thermal overload is displayed via the
operator panel and parameter
played as soon as the value of
reached. Multifunction input 2 can be reached as input for tempera-
ture measurement with a measuring resistor PT1000. The input
signal must be analog. Parameter
the actual value.
Temperature measurement. The frequency inverter is switched off
immediately as soon as the value of
617 is reached. The error switch-off is displayed by message F0400.
Multifunction input 2 can be reached as input for temperature
measurement with a measuring resistor PT1000. The input signal
must be analog. Parameter
actual value.
Temperature measurement. The frequency inverter is switched off
as soon as the value of
Max. Temp. Motor Winding
The error switch-off is displayed by message F0400. The error
switch-off is delayed by one minute. Multifunction input 2 can be
reached as input for temperature measurement with a measuring
resistor PT1000. The input signal must be analog. Parameter
226 shows the actual value.
ing Temperature
103 which is assigned a logic signal or a digital input
570, multifunction input 2 cannot be used for other
139
Function
Max. Temp. Motor Winding
Winding Temperature
617 is reached.
269. The warning is dis-
Warnings
Max. Temp. Motor Winding
Winding Temperature
Max. Temp. Motor Winding
226 shows the
Winding Temperature
617 is reached.
06/2013
Operating Instructions
226 shows
617 is
226 shows
Wind-
Agile