Parameter descriptions
Signal source
76 - MFI1D
Assign to a function, e.g. select signal source for parameter.
7.6.2

Multifunction input MFI2

562 Operation Mode MFI2 (Multifunction input 2)
Multifunction input MFI2 can be configured as a voltage, current or a digital input. In the configuration
as a digital input, the evaluation can be selected as PNP (high-switching) or NPN (low-switching).
Depending on the selected
can be controlled.
Operation Mode MFI2
1 - Voltage 0...10 V
2 - Current 0...20 mA
3 - Digital NPN (active: 0 V)
4 - Digital PNP (active: 24 V)
5 - Current 4...20 mA
6 - Voltage, characteristic
7 - Current, characteristic
By default, multifunction input MFI2 is set as a digital input for connection of a motor thermal contact.
Alternatively, you can select the operation mode for an analog voltage or current signal. The current
signal is continuously monitored and the fault message "F1407" displayed if the maximum figure is
exceeded.
7.6.2.1

Multifunction input set as analog input MFI2A

The Multifunction input can be evaluated either as analogue or digital signal. In the following the
evaluation for analogue signals is described.
7.6.2.1.1 Voltage input and current input
For parameter
Operation Mode MFI2
rent 4...20 mA" must be selected.
Operation Mode MFI2
1 - Voltage 0...10 V
2 - Current 0...20 mA
5 - Current 4...20 mA
Control inputs and outputs
562, various functions of the frequency inverter
Operation Mode MFI2
562
Voltage signal (MFI2A), 0 V ... 10 V. Fixed characteristic.
Current signal (MFI2A), 0 mA ... 20 mA. Fixed characteristic.
Digital signal (MFI2D) 0 V ... 24 V. Low-switching (with negative
signal). Factory setting.
Digital signal (MFI2D) 0 V ... 24 V. High-switching (with positive
signal).
Current signal (MFI2A), 4 mA ... 20 mA. Fixed characteristic
Voltage signal (MFI2A), 0 V ... 10 V. The output signal is influ-
enced by the set characteristic. The characteristic can be set via
parameters 564 ... 567.
Current signal (MFI2A) 0 mA ... 20 mA. The output signal is in-
fluenced by the set characteristic. The characteristic can be set
via parameters 564 ... 567.
562, "1 - Voltage 0...10 V", "2 - Current 0...20 mA" or "5 - Cur-
562
Voltage signal (MFI2A), 0 V ... 10 V. Fixed characteristic.
Current signal (MFI2A), 0 mA ... 20 mA. Fixed characteristic.
Current signal (MFI2A), 4 mA ... 20 mA. Fixed characteristic