Commissioning
Starting behaviour (field-oriented)
P623
Starting Current (value: I
For sufficient torque if a high start torque is re-
quired. The start current is impressed until the
output frequency reaches the value of P624.
P624
Frequency Limit (2.60 Hz)
The starting current is impressed up to this output frequency.
779
Min. Flux-Formation Time
The current during flux-formation (P781) is impressed at least for this time.
P780
Max. Flux-Formation Time (P30=410: 1000 ms), (P30=610: 50 ms)
The current during flux-formation (P781) is impressed not longer than this time.
P781
Current during flux-formation (value: I
Upon startup, this current value is impressed. The time for current impression is limited
by P780.
Stopping behaviour
P630
0
P68 and P69 = 1: Coast to Stop, P68 and P69 = 0: Coast to Stop
1
P68 and P69 = 1: Coast to Stop, P68 and P69 = 0: Stop and Switch Off
...
11
P68 and P69 = 1: Stop and Switch Off, P68 and P69 = 0: Stop and Switch Off
...
43
P68 and P69 = 1: Emergency Stop and Switch Off, P68 and P69 = 0: Stop and
DC brake
DC brake (only if P30 = 110): As from standstill, the direct current P631 (brak-
ing current) is impressed for the time of P632 (braking time).
Via P68 (Start Clockwise) and P69 (Start Anticlockwise) the motor stopping behavior is
controlled. For state P68 and P69 = logic 1, a stopping behavior must be selected. For
state P68 and P69 = logic 0, a stopping behavior must be selected.
1
Nominal value of frequency inverter
After first commissioning
if
P30: 410 - IM: sensor-less field-oriented control"
P30: 610 - PMSM: sensor-less field-oriented control"
1
)
FIN
)
FIN
89
(Factory setting)
(Factory setting)
06/2013
Operating Instructions
Agile