The analog input signal is mapped to a reference frequency or percentage.
The analog input signal is mapped to a reference frequency or percentage.
Voltage 0...10 V
Parameter
Operation Mode MFI1
relate, as a percentage, to the analog signal with 9.8 V and parameter
parameter
Maximum Reference Percentage
age value lies at 0.2 V. The deviations from 10 V and 0 V allow the operation even with voltage sup-
plies that have small deviations from the nominal values.
9.8 − 0.2
Incliniation:
Current 0...20 mA
Current 0...20 mA
Parameter
Operation Mode MFI1
points relate, as a percentage, to the analog signal with 19.6 mA and parameter
419 or parameter
cy
Maximum Reference Percentage
percentage value lies at 0.4 mA. The deviations from 20 mA and 0 mA allow the operation even with
19.6 − 0.4
voltage supplies that have small deviations from the nominal values.
Incliniation:
Current 4...20 mA
Parameter
Operation Mode MFI1
points relate, as a percentage, to the analog signal with 19.6 mA and parameter
419 or parameter
Maximum Reference Percentage
percentage value lies at 4.4 mA. The deviations from 20 mA and 4 mA allow the operation even with
voltage supplies that have small deviations from the nominal values.
19.6 − 4.4
Incliniation:
Agile
Operating Instructions
452 is set to "1 - Voltage 0...10 V". The coordinates of the points
519. The zero-crossing of the frequency or the percent-
= �
419
452 must be set to "2 - Current 0...20 mA". The coordinates of the
19.2
= �
419
452 must be set to "5 - Current 4...20 mA". The coordinates of the
15.2
= �
419
f [Hz]
50 Hz
P562=1
0 V
0.2 V
(P562=2)
(0 mA)
(P562=5)
(20 mA)
176
06/2013
Maximum Frequency
9.6
= �
. 519
519. The zero-crossing of the frequency or the
= �
. 519
519. The zero-crossing of the frequency or the
= �
. 519
9.8 V
U [V]
+10 V
(+20 mA)
(+20 mA)
Control inputs and outputs
Parameter descriptions
419 or
9.6
Maximum Frequen-
19.2
Maximum Frequency
15.2
Need help?