Starting behaviour (V/f)
The motor is magnetized (flux-formation, P781) and, if selected, a starting current
(P623) is impressed. The IxR compensation compensates the voltage drop at the stator
resistor.
P620
Operation Mode
0
Off
1
Magnetization
2
Magnetization +Current Impression
3
Magnetization + IxR-Compensation
4
Magnetization + Current Impression +
IxR-Compensation
12
Magnetization +Current Impression
with Ramp Stop
14
Magnetization + Current Impression
with Ramp Stop + IxR-Compensation
P623
Starting Current (value: I
For sufficient torque if a high start torque is re-
quired. The start current is impressed until the
output frequency reaches the value of P624.
P624
Frequency Limit (2.60 Hz)
The starting current is impressed up to this output frequency.
P780
Max. Flux-Formation Time (300 ms)
The current during flux-formation (value of P781) is not impressed longer than this
time.
P781
Current during Flux-Formation (value: I
Upon startup, this current value is impressed. The time for current impression is limited
by P780.
1
Nominal value of frequency inverter
Agile
Operating Instructions
if
P30: 110 - IM: sensor-less control (SLC), V/f characteristic
1
)
FIN
)
FIN
88
06/2013
(Factory setting)
Control according to V/f characteristic.
Set P780 and P781.
Set P623, P624, P780 and P781.
Set P624, P780 and P781.
Set P623, P624, P780 and P781.
Set P623, P624, P780 and P781.
For high start torque.
Set P623, P624, P780 and P781.
For high start torque.
PI controller for start current
P621
P part (2.00)
P622
I part (50 ms)
After first commissioning
Commissioning