Parameter descriptions
623 Starting current
623 ensures, particularly for high-torque start, a sufficient torque until the
The
Starting current
624 is reached.
quency limit
Applications in which high current is permanently needed at a low speed are to be realized using
forced-ventilated motors to prevent thermal overload.
Parameters
No.
Description
623 Starting current
I
: Nominal value of frequency inverter
FIN
o
: Overload capacity of frequency inverter.
c
In the following settings, the starting current impression is used for the starting behavior:
30 = "110 - IM: sensor-less control" (V/f control of asynchronous motor),
Configuration
620 =2, 4, 12 or 14
Operation mode
30= "410 - IM: sensor-less field-orientated control (DMC)", asynchronous motor
Configuration
30= "610 - PMSM: sensor-less field-orientated control (DMC)", synchronous motor
Configuration
624 Frequency limit
The
623 is impressed until the
Starting current
points below the frequency limit are only permissible if forced-ventilated motors are used.
The transition to the control method of the selected
cy limit.
The
624 is set up automatically during the guided motor commissioning in field ori-
Frequency limit
ented control configurations 410 and 610. In V/f control configuration 110 the parameter
624 is not changed by the guided motor commissioning.
limit
Parameters
No.
Description
624 Frequency Limit
In the following settings, the starting current impression is used for the starting behavior:
30 = "110 - IM: sensor-less control" (V/f characteristic of asynchronous motor),
Configuration
620 =2, 3, 4, 12 or 14
Operation mode
30= "410 - IM: sensor-less field-orientated control (DMC)", asynchronous motor
Configuration
30= "610 - PMSM: sensor-less field-orientated control (DMC)", synchronous motor
Configuration
625 Brake release time
In order to protect the motor holding brake against damage, the motor may only start after the brake
has been released. Startup to reference speed is effected only after the
elapsed. The time should be set such that it is at least as long as the time required for releasing the
holding brake. By using negative values for the parameter, release of the brake is delayed. This can
be done in order to prevent loads from falling down, for example.
Parameters
No.
Description
625 Brake release time
Operational Behavior
Setting
Min.
Max.
0.0 A
o
⋅I
c
FIN
624 is reached. Permanent operating
Frequency limit
30 takes place above the frequen-
Configuration
Setting
Min.
Max.
0.00 Hz
100.00 Hz
Setting
Min.
Max.
-5000 ms
5000 ms
125
06/2013
Fact. sett.
I
FIN
Frequency
Fact. sett.
2.60 Hz
625 has
Brake release time
Fact. sett.
0 ms
Agile