Parameter descriptions
WARNING
The monitoring of the analog input signal via the parameter
563 demands the check of parameter
Example:
Error/warning behavior
1V/2mA". In the factory settings of the parameter
or error switch-off are effected at an output frequency ≠ 0 Hz. If shutting down or error switch-off are
to be effected at an output frequency of 0 Hz, the Point X1 must be adjusted (e.g. X1=10% /1 V).
7.6.2.2
Multifunction input set as digital input MFI2D
Multifunction input MFI2 (terminal X12.4) can be configured as a digital input. Via parameter
562, the evaluation can be selected as PNP (high-switching) or NPN (low-switching).
tion Mode MFI2
The multifunction input set as digital input can be linked to the functions of the frequency inverter.
Signal "77 - MFI2D" must be assigned a function.
In the factory settings, signal "532 - MFI2D (Hardware)" is assigned to parameter
204.
P570
Operation Mode MFI2
3 - Digital NPN (active: 0 V)
4 - Digital PNP (active: 24 V)
Signal source
MFI2D
532 -
(Hardware)
77 - MFI2D
Control inputs and outputs
563 = "2 - Shutdown < 1V/2mA" or "3 - Error-Switch-Off <
Y
50 Hz
(X1=2%/Y1=0%)
0 Hz
0.2 V
1 V
562
Digital signal (MFI2D) 0 V ... 24 V. Low-switching (with negative
signal). Factory setting.
Digital signal (MFI2D) 0 V ... 24 V. High-switching (with positive
signal).
Assign to a function, e.g. select signal source for parameter. Factory setting:
Thermal contact for P570
Assign to a function, e.g. select signal source for parameter.
Characteristic Curve Point X1
Characteristic Curve Point X1
X
9.8 V
Function
Function
204= "532 - MFI2D (Hardware)".
181
06/2013
Operating Instructions
Error/Warning Behaviour
564.
564 shutting down
Opera-
Thermal contact for
Agile