Parameter descriptions
If an error is signaled in a branch both for positive and negative current, the relevant load branch
circuit is open (e.g. broken wire) or the relevant current measurement is defective. If an error is sig-
naled in a branch for one polarity only, an IGBT or driver is defective or a connection in the device is
interrupted.
The impressed direct current is 25% of the peak value of the rated current. The rated current must be
set with parameter
Rated Current
In order to prevent damage of the device and the load, the output voltage is limited. If the set current
(see above) cannot be reached with this voltage due to a high ohmic resistance of the load, an open-
circuit error is identified in each branch. In this case, the current to be impressed must be reduced by
changing parameter
Rated Current
Message
T0001
Stop. Test stopped by user.
T0002
Permanent error. Non-acknowledgeable error present. No (further) test possible.
T0003
Signals on digitals inputs STOA and STOB for enable missing. No enable.
T0010
At the beginning of the test an inadmissible current flows.
T0201
U open. It was not possible to impress a positive current in branch U.
T0202
V open. It was not possible to impress a positive current in branch V.
T0203
W open. It was not possible to impress a positive current in branch W.
T0204
-U open. It was not possible to impress a negative current in branch U.
T0205
-V open. It was not possible to impress a negative current in branch V.
T0206
-W open. It was not possible to impress a negative current in branch W.
T0211
U short-circuit. Short-circuit cutoff during impression of positive current in branch U.
T0212
V short-circuit. Short-circuit cutoff during impression of positive current in branch V.
T0213
W short-circuit. Short-circuit cutoff during impression of positive current in branch W.
T0214
-U short-circuit. Short-circuit cutoff during impression of negative current in branch U.
T0215
-V short-circuit. Short-circuit cutoff during impression of negative current in branch V.
T0216
-W short-circuit. Short-circuit cutoff during impression of negative current in branch W.
T0221
Earth fault Phase U. Earth fault cutoff during impression of positive current in branch U.
T0222
Earth fault Phase V. Earth fault cutoff during impression of positive current in branch V.
T0223
Earth fault Phase W. Earth fault cutoff during impression of pos. current in branch W.
T0224
-U earth fault. Earth fault cutoff during impression of negative current in branch U.
T0225
-V earth fault. Earth fault cutoff during impression of negative current in branch V.
T0226
-W earth fault. Earth fault cutoff during impression of negative current in branch W.
T0231
U Soft earth fault. The DC-link voltage has increased. Insulation problem in motor.
T0232
V Soft earth fault. The DC-link voltage has increased. Insulation problem in motor.
T0233
W Soft earth fault. The DC-link voltage has increased. Insulation problem in motor.
T0234
-U Soft earth fault Phase U. Insulation problem in motor.
T0235
-V Soft earth fault Phase V. Insulation problem in motor.
T0236
-W Soft earth fault Phase W. Insulation problem in motor.
T0260
Asymmetric phase voltages.
Err.S41
Internal error. Abort and restart the test.
If Test 2 signals an earth fault while Test 1 did not signal an earth fault, a current measurement will
probably be defective.
If Test 2 signals a short-circuit, there is either a short-circuit in the load or a current measurement is
defective.
Machine data
371 in data set 1.
371.
Meaning
119
06/2013
Operating Instructions
Agile