Problem
Motor does not
Parameter setting
turn after a start
command at digi-
tal input.
Reference value too low.
No enable
Error in control cables
Motor does not produce
enough torque.
Motor does not
Parameter setting
turn after a start
command via a
No enable
communication
interface
Motor turning in
Incorrect connection of
wrong direction.
motor phases.
Parameter setting
Motor turning in
Parameter setting
one direction
only.
Agile
Operating Instructions
Cause
Select correct source for reference value.
For example, for speed setting via a multifunction
input, set at least one of parameters P475 or P492 to
"1 - analog input 1" (terminal X12.3) or "2 - analog
input 2" (terminal X12.4).
For P452 (terminal X12.3) and P562 (terminal X12.4),
select the correct signal to set the reference value
("1 - voltage" or "2 - current").
For P68 (Start clockwise) or P69 (Start anticlock-
wise), select the required digital input.
Check P418 (Minimum frequency).
Set digital input for the start command to the re-
quired evaluation ("0 - NPN" or "1 - PNP").
Check actual value P228 (internal reference frequen-
cy). Check voltage or current value at reference val-
ue input.
Switch on both enable inputs STOA and STOB.
Check control cable connections.
Carry out setup (again).
Long cables will reduce the torque.
V/f characteristic: Check start-up behavior (P620),
flux-formation (P780 and P781) and starting current
(P623).
Field-orientated control: Check start-up behavior
(flux-formation P780 and P781) and torque limit
(P730), reset to factory settings if necessary.
Via P412 set the controller to "1 - state machine" or
"2 - remote contacts".
Switch on both enable inputs STOA and STOB.
Check motor cables.
Exchange two motor phases (e.g. U and V) at the
frequency inverter terminals.
Connect terminals U, V and W of the frequency in-
verter to the corresponding terminals U, V and W of
the motor.
Check if P493 or P495 is set to "3 - Inverted". The
reference value will be inverted.
Check if for P68 (Start clockwise) and P69 (Start
anticlockwise) the required digital inputs are select-
ed.
Check the characteristic parameters if the reference
value is defined via MFI1 or MFI2 and "6 - voltage
characteristic" or "7 - current characteristic" is select-
ed.
Check if P493 or P495 is set to "2 - positive only". In
this case, the reference value can only be positive.
Factory setting: "1 - (+/- reference value)".
Check values for P420 (acceleration clockwise) and
P422 (acceleration anticlockwise). The value
0.00 Hz/s blocks the corresponding direction of rota-
tion.
332
06/2013
Error protocol
Possible remedy
Troubleshooting