Parameter
Ramp gradient. Change rate [Hz/s] of output frequency after a
change of the reference value or after a stop or brake command.
P418
Minimum Frequency in Hz.
Minimum motor speed [Hz]. The frequency will not drop below this
value even if a lower reference frequency is selected.
P419
Maximum Frequency in Hz.
Maximum motor speed [Hz]. The frequency will not rise above this
value even if a higher reference frequency is selected.
Commissioning (Setup) complete and ready for operation.
Finish the guided commissioning. The device executes a reset. 2 sec-
onds after the message "done" is visible, the reset is done automati-
cally.
Drive enabled.
− For further setting options, select "Para" menu or
− start the drive. Via the operator panel or via signals at control
terminals.
Start motor via operator panel:
Select "local" menu for manual operation.
Select "Poti F" (motor potentiometer) menu.
Switch on STOA (X11.3) and STOB (X13.3).
Press RUN button.
The motor is accelerated to the value of P418 (minimum frequency).
Factory setting 3.50 Hz.
Using the arrow keys, set the speed.
Start the drive via signals at control terminals:
Switch on Start clockwise at IN1D (X11.4) or
Start anticlockwise at IN2D (X11.5).
The motor is accelerated to the value of P418 (minimum frequency).
Factory setting 3.50 Hz.
By means of a voltage 0 ... 10 V on MFI1 (X12.3) set the speed. For
potentiometer connection refer to chapter 5.7.1 "Circuit for control
via control terminals".
Optional optimization of motor characteristics
The motor characteristics are set correctly for most of the applications with the default settings. In
some cases optimization of the motor characteristics can be necessary or improve the performance
significantly. The optimization possibilities are described in chapter 6.2.10.