Applications; Pump - BONFIGLIOLI Agile Operating Instructions Manual

Frequency inverter 230 v / 400 0.09 kw ... 11 kw
Hide thumbs Also See for Agile:
Table of Contents

Advertisement

Commissioning
6.7

Applications

The parameters required for typical applications are listed. Selecting an application makes commis-
sioning easier. Depending on the application, additional settings may be required.
Note
The PC software VPlus provides application masks for easy commissioning of applications.

6.7.1 Pump

Parameters
30 Configuration
420 Acceleration (clockwise)
421 Deceleration (clockwise)
492 Reference frequency source 2
Operation mode (reference frequency
493
source)
418 Minimum frequency
419 Maximum frequency
420 Acceleration (clockwise)
447 1st Blocking frequency
449 Frequency Hysteresis
475 Reference frequency source 1
606 Type V/f characteristic
Operation mode (P68&P69=1
630
|P68&P69=0) (stopping behavior)
651 Operation mode (auto start)
1550 Operation mode energy saving function 2 - Automatic
1552 Energy saving function on
68 Start Clockwise
69 Start Anticlockwise
Operation mode OUT1D (X13.5) (digital
531
output)
532 Operation mode OUT2D (X10/relay)
Applications
Recommenced setting
110 IM: sensorless control (V/f characteristic)
10 Hz/s
-0.01 Hz
0 - Zero
1 - (+/- reference)
10 Hz
53 Hz
10 Hz/s
0 Hz
0 Hz
1 - Analog Value MFI1A
2 - quadratic
11 - (Stop, Off | Stop, Off)
0 - Off
163 - Reference Frequency reached
71 - IN1D
7 - Off
2 - Run signal
103 - Inv. error signal
99
06/2013
Operating Instructions