Advertisement

Service
Operation Mode Service In-
1535
terval Fan
0 - No Action
Service Parameter
1 -
Message
2 - Alarm Message
Parameter
Maintenance Note
the fan has not elapsed and no service is required.
Warning signal
Expiry of the time remaining until service is signaled.
265 -
Warning service
51 -
fan
Operation mode service interval fan
Service interval remaining until next service
1531 Service Interval Fan
Parameter
Service Interval Fan
percent of maintenance interval. If a value of 0% is displayed, service is required. It should also be
checked if the component must be replaced.
The service interval remaining until service is an estimated value. The service interval
actually remaining until next service also depends on the ambient conditions, for ex-
ample. As a result, the indicated service interval until next service may be too high.
Service the fan regularly. See chapter 10.2 "Regular service work".
The service interval remaining until service (parameter
100% if setting "2 - fan" is selected for parameter
Monitoring of service interval
The service interval remaining until service is monitored. The re-
maining service interval until service can be indicated via parameter
Service Interval Fan
The service interval remaining until service is monitored. The re-
maining service interval until service can be indicated via parameter
Service Interval Fan
service has expired, parameter
the message "M0002 Service fan". Factory setting.
The service interval remaining until service is monitored. The re-
maining service interval until service can be indicated via parameter
Service Interval Fan
service has expired:
− Parameter
Maintenance Note
"M0002 Service fan".
− A warning message will be output and a warning signal will be
set. The warning will also be displayed on the operator panel.
1533 displays message "M0000" if the remaining time until service of
For linking to frequency inverter functions.
For output via a digital output. Select the signal source for one of the
parameters 531, 532, 533, or 554.
See chapter 7.6.5 "Digital outputs".
1534 must be set to "2 - Warning".
1531 indicates the service interval remaining until next service in
Reset Service Intervals
275
Function
1531. No service info or message is output.
1531. As soon as the remaining time until
Maintenance Note
1531. As soon as the time remaining until
1533 will show the message
Service Interval Fan
1539.
06/2013
Operating Instructions
1533 will show
1531) can be set to
Agile