Output signals
The output of a warning is signaled.
1)
215 - Warning
mask, appli-
2)
27 -
cation
1)
For linking to frequency inverter functions.
2)
For output via a digital output. Select the signal source for one of the parameters 531, 532, 533,
554. See chapter 7.6.5 "Digital outputs".
Parameter
from the created Warning mask.
7.6.6

Digital inputs

The assignment of the control signals to the available software functions can be adapted to the appli-
cation in question. In addition to the available digital control inputs, further internal logic signals are
available as sources.
Each of the individual software functions is assigned to the various signal sources via parameterizable
inputs. This enables a flexible use of the digital control signals.
559 Digital inputs PNP/NPN
Via parameter
Digital inputs PNP/NPN
PNP (high-switching) or NPN (low-switching).
Terminal
Digital inputs PNP/NPN
X11.4
0 - NPN (active: 0 V)
X11.5
X11.6
X12.1
1 - PNP (active: 24 V)
X12.2
In order to use multifunction input MFI1 as a digital input, setting 3 or 4 must be selected for parame-
ter
Operation Mode MFI1
Terminal
Operation Mode MFI1
3 - Digital NPN (active: 0 V)
X12.3
4 - Digital PNP (active: 24 V)
In order to use multifunction input MFI2 as a digital input, setting 3 or 4 must be selected for parame-
ter
Operation Mode MFI2
Terminal
Operation Mode MFI2
3 - Digital NPN (active: 0 V)
X12.4
4 - Digital PNP (active: 24 V)
In order to use the digital input/output (terminal X11.6) as a digital input, setting "0 - Input IN3D"
must be selected for parameter
Terminal
Operation Mode Terminal X11.6
X11.6
0 - Input IN3D
For setting of X11.6 as digital output, refer to chapter 7.6.4 "Digital input/output IN3D/OUT3D".
Agile
Operating Instructions
Output of warning activated in
Warning Application
559, the evaluation at the digital inputs can be selected as
559
Digital input NPN. Low-switching (with negative sig-
nal).
Digital input PNP. High-switching (with positive sig-
nal). Factory setting.
452.
452
562.
562
Operation Mode Terminal X11.6
196
06/2013
Create Appl. Warning Mask
273 shows the Application Warnings independent
Function
Function
Low-switching (with negative signal).
High-switching (with positive signal).
Function
Low-switching (with negative signal). Factory
setting.
High-switching (with positive signal).
558.
558
Function
The digital input/output is set as digital in-
put. Factory setting.
Parameter descriptions