BONFIGLIOLI Agile Operating Instructions Manual page 199

Frequency inverter 230 v / 400 0.09 kw ... 11 kw
Hide thumbs Also See for Agile:
Table of Contents

Advertisement

Parameter descriptions
Control signals
Selection for parameter
Inverter Re-
525 -
lease(Hardware)
526 - IN1D (Hardware)
527 - IN2D (Hardware)
528 - IN3D (Hardware)
529 - IN4D (Hardware)
530 - IN5D (Hardware)
531 - MFI1D (Hardware)
532 - MFI2D (Hardware)
537 to 544
640
Out-PZD3 Boolean
to
to
655
Out-PZD18 Boolean
700 - RxPDO1 Boolean1
701 - RxPDO1 Boolean2
702 - RxPDO1 Boolean3
703 - RxPDO1 Boolean4
710 to 713
720 to 723
730 - Sysbus emergency
810
Obj 0x3003 DigOut 1 to
to
Obj 0x3003 DigOut 5
814
832
Obj 0x3005 Demux
to
Out 1 to Obj 0x3005
847
Demux Out 16
910
Output DeMux bit 0
to
to
925
Output DeMux bit 15
2401
PLC-Output Buffer 1
to
to
2416
PLC-Output buffer 16
1
The digital signal is independent from the configuration of the parameter
2
Refer to instructions on Profibus.
3
Refer to instructions on system bus.
4
Refer to instructions on CANopen.
5
Refer to instructions on system bus or Profibus.
6
Refer to application manual PLC.
Control inputs and outputs
Enable signal of the frequency inverter via digital inputs STOA
(X11.3) and STOB (X13.3).
Signal at digital input IN1D (X11.4).
Signal at digital input IN2D (X11.5).
Signal at digital input IN3D (digital input/output, X11.6) in
eration Mode Terminal X11.6
Signal at digital input IN4D (X12.1).
Signal at digital input IN5D (X12.2).
1
Signal at multifunction input MFI1 (X12.3) in
452 "3 - Digital NPN (active: 0 V)" or "4 - Digital PNP
MFI1
(active: 24 V)".
Signal at multifunction input MFI2 (X12.) in
562 "3 - Digital NPN (active: 0 V)" or "4 - Digital PNP
MFI2
(active: 24 V)".
Operation modes 525 to 532 of the digital inputs inverted (LOW
active).
Process data for Profibus communication. Optional communica-
2
tion module CM-PDP-V1 with Profibus interface is required.
Process data object for system bus communication.
Process data object for system bus communication.
Process data object for system bus communication.
3
Process data object for system bus communication.
Operation modes 700 to 703 for RxPDO2.
Operation modes 700 to 703 for RxPDO3.
Signal of system bus communication.
Sources of CAN objects for CANopen® communication.
4
Sources at output of demultiplexer for CANopen® communica-
tion.
Bit 0 to Bit 15 on output of de-multiplexer; de-multiplexed pro-
5
cess data signal via system bus or Profibus on input of multi-
plexers (parameter
DeMux Input
6
Output signals of PLC-functions.
199
Function
558 = "0 - Input IN3D".
Operation Mode
Operation Mode
1253).
.
412
Local/Remote
06/2013
Operating Instructions