Error Messages During Commissioning (Sf - BONFIGLIOLI Agile Operating Instructions Manual

Frequency inverter 230 v / 400 0.09 kw ... 11 kw
Hide thumbs Also See for Agile:
Table of Contents

Advertisement

6.2.6

Error messages during commissioning (SF...)

If an error or a warning is signaled during commissioning, the following causes are possible.
Code
Message
Rated current
SF001
too low
Rated current
SF002
too high
SF003
Rated cos-phi
Negative slip
SF004
frequency
Slip frequen-
SF005
cy too high
Power bal-
SF006
ance
Config. not
SF007
supported
Inductance
SF011
measurement
failed
Inductance
SF012
measurement
failed
Resistance
SF021
measurement
failed
Resistance
SF022
measurement
failed
Setup abort-
SF026
ed
If an error or a warning is signaled:
− Press ESC to correct a parameter value after an error message or warning.
− Press ENT to suppress a warning message. Setup is continued. It is recommended that the entered
data be checked.
In the case of problems not triggering an error message, you can try to find an appropriate measure,
following the instructions in chapter 13.3 "Troubleshooting".
If errors or warning messages occur during operation, proceed according to the instructions in chap-
ters 13.1.1 "Error messages" and 14.3 "Warning status and warning status application".
Agile
Operating Instructions
Error messages
The value entered for parameter
value.
The value for parameter
eters
376 and
Rated Power
The value entered for parameter
than 1 or smaller than 0.3). Correct the value.
The calculated slip frequency is negative. Check and, if necessary, correct
the values entered for parameters
375.
The calculated slip frequency is too high. Check and, if necessary, correct
the values entered for parameters
375.
The calculated total output of the drive is lower than the rated power. Cor-
rect and check, if necessary, the value entered for parameter
376.
The set configuration is not supported by the set-up routine.
The main inductance measurement has failed because the motor has a high
slip. Correct the rated motor values in parameters 370, 371, 372, 374,
375 and 376. Carry out the set-up routine again. In case an error message
is displayed again, enter the value 110 for parameter
(sensorless control according to V/f-characteristic) if value 410 was set so
far. Carry out the set-up routine again.
The leakage inductance measurement has failed because the motor has a
high slip. Correct the rated motor values in parameters 370, 371, 372,
374, 375 and 376. Carry out the set-up routine again. In case an error
message is displayed again, enter the value 110 for parameter
30 (sensorless control according to V/f-characteristic) if value 410 was
tion
set so far. Carry out the set-up routine again.
The measurement of the stator resistance did not deliver a plausible value.
Check the cables at the terminals of the motor and the frequency inverter
for proper connection and check the contacts for corrosion and safe con-
tact. Carry out the set-up routine again.
The measurement of the rotor resistance did not deliver a plausible value.
Check the cables at the terminals of the motor and the frequency inverter
for proper connection and check the contacts for corrosion and safe con-
tact. Carry out the set-up routine again.
The setup-routine is aborted.
70
06/2013
Meaning
371 is too low. Correct the
Rated Current
371 is too high, referred to param-
Rated Current
370. Correct the values.
Rated Voltage
Rated Cosine Phi
372 and
Rated Speed
372 and
Rated Speed
Commissioning
374 is wrong (greater
Rated Frequency
Rated Frequency
Rated Power
30
Configuration
Configura-
First commissioning