Commissioning
SA003 Rated cos-phi
Slip frequen-
SA004
cy
Stator re-
SA021
sistance high
value
Rotor re-
SA022
sistance high
value
Rated Slip
Correction
SA041
Factor low
value
Rated Slip
Correction
SA042
Factor high
value
Check motor
SA051
connection
Check motor
SA052
connection
Check motor
SA053
connection
If an error or a warning is signaled:
− Press ESC to correct a parameter value after an error message or warning.
− Press ENT to suppress a warning message. Setup is continued. It is recommended that the entered
data be checked.
In the case of problems not triggering an error message, you can try to find an appropriate measure,
following the instructions in chapter 13.3 "Troubleshooting".
If errors or warning messages occur during operation, proceed according to the instructions in chap-
ters 13.1.1 "Error messages" and 14.3 "Warning status and warning status application".
First commissioning
Warning Messages
The value entered for parameter
normal range (0.6 to 0.95). Correct the value.
For an asynchronous motor, the calculated slip is in the limit range. Check
372 and
Rated Speed
Rated Frequency
The following causes are possible: The motor cable cross-section is not
sufficient. The motor cable is too long. The motor cable is connected incor-
rectly.
The following causes are possible: The motor cable cross-section is not
sufficient. The motor cable is too long. The motor cable is connected incor-
rectly.
Check
372 and
Rated Speed
372 and
Check
Rated Speed
The motor data for star connection were entered, the motor, however, is
connected in delta. Change motor cable connections for star connection.
Check motor data entered for delta connection. Repeat commissioning
(Setup) via operator panel.
The machine data for delta connection were entered, the motor, however,
is connected in star. Change motor cable connections for delta connection.
Check motor data entered for star connection. Repeat commissioning (Set-
up) via operator panel.
Check connections at frequency inverter and motor.
69
374 is outside of the
Rated Cosine Phi
375.
375.
Rated Frequency
375.
Rated Frequency
06/2013
Operating Instructions