Digital inputs (X210A.3 ... X210B.2): Low signal: DC 0 V ... 3 V, High signal: DC 12 V ... 30 V,
input resistance: 2,3 kΩ, response time: 2 ms (STOA and STOB: 10 ms), PLC-compatible
Digital output (X210B.3): Low signal: DC 0 V... 3 V, High signal: DC 12 V ... 30 V,
maximum output current: 50 mA, PLC-compatible
Multi-function output (X210B.4):
Analog signal: DC 19 V... 28 V, maximum output current: 50 mA, pulse width modulated (f
Digital signal: Low signal: DC 0 V... 3 V, High signal: DC 12 V ... 30 V, maximum output current: 50 mA,
PLC-compatible,
Frequency signal: output voltage: DC 0 V ... 24 V, maximum output current: 40 mA,
Maximum output frequency: 150 kHz
Multi-function input (X210B.6):
Analog signal: input voltage: DC 0 V ... 10 V (R
Digital signal: Low signal: DC 0 V... 3 V, High signal: DC 12 V ... 30 V, response time: 4 ms, PLC-compatible
Conductor cross section:
Suitable conductor cross sections for the control terminals are:
With wire end ferrule: 0.25...1.0 mm²
Without wire end ferrule: 0.14...1.5 mm²
3.7.1

External 24 VDC voltage supply

The bidirectional control terminals X210A.1/X210A.2 can be used as voltage output or voltage input. If an exter-
nal 24 VDC voltage supply is connected to the terminals X210A.1/X210A.2 the parameterisation and communica-
tion is possible and input and outputs are active, even if the mains voltage is switched off.
The specification of technical requirements of the external voltage supply can be found in the operating instruc-
tions manual.
Input voltage range
Input rated current
Inrush current peak
External fuse protection
Safety
36
36
Technical Data of the control terminals
=70 kΩ), input current: DC 0 mA ... 20 mA (R
i
Requirements of the external voltage supply
24 VDC ±10%
Max. 1.1 A
Typical: < 25 A
Via commercial available circuit breakers for rated current, charakteristic: slow-
acting
Extra safety low voltage (SELV) according to EN 61800-5-1
= 116 Hz),
PWM
=500 Ω),
i
09/08
09/08