BONFIGLIOLI Agile Operating Instructions Manual page 223

Frequency inverter 230 v / 400 0.09 kw ... 11 kw
Hide thumbs Also See for Agile:
Table of Contents

Advertisement

Parameter descriptions
478 Actual Percentage Source, PID real value input
The analog input or the repetition frequency input to which the PID real value is applied can be se-
lected via parameter
Actual Percentage Source
bus system.
Actual Percentage Source
1 - Analog Input MFI1A
2 - Analog Input MFI2A
32 - Rep. Percentage Input
40 - Actual Percentage RAM
704 - RxPDO1 Word 1
705 - RxPDO1 Word 2
2521 - PLC-Output Percentage 1
2522 - PLC-Output Percentage 2
Control functions
478. The actual value can also be transmitted via a
478
Analog signal at multifunction input 1 (terminal X12.3). Factory
setting. Via parameter
must be set up as an analog input (voltage or current). See
chapter 7.6.1 "Multifunction input MFI1".
Analog signal at multifunction input 2 (terminal X12.4). Via pa-
rameter
Operation mode MFI2
as an analog input (voltage or current). See chapter 7.6.2
"Multifunction input MFI2".
Percentage signal at digital input IN2D. Evaluation can be se-
lected via parameter
7.6.7.2 "Repetition frequency input".
Value of parameter
529 can be set via Fieldbus, but is not visible in
centage RAM
VPlus or the keypad.
Process data from system bus. Refer to system bus instructions.
Process data from system bus. Refer to system bus instructions.
Output value of a PLC-function. Percentage output 1 of the
table function is the PID real value source. See application
manual "PLC".
Output value of a PLC-function. Percentage output 2 of the
table function is the PID real value source. See application
manual "PLC".
223
Function
Operation mode MFI1
562, the input must be set up
496. See chapter
Operation mode IN2D
Actual Percentage RAM
06/2013
Operating Instructions
452, the input
529.
Actual Per-
Agile