Step 5: Run the Motor

Make sure the power is OFF, and that it cannot be switched on accidentally whilst you are working.

The Autotune Feature

Note
The drive will not perform an Autotune when in Volts/Hz Mode (Open-Loop Drive.) An Autotune is not
necessary in this control mode.
The Autotune feature identifies motor characteristics to allow the drive to control the motor.
It loads the values into the parameters below, which are in the QUICK SETUP menu.
PREF
71.03
27.06
27.14
27.15
27.16
27.17
For further information on the functions of all parameters, refer to Appendix D: "Programming".
890SD (Standalone) Drive: Frame G, H & J
Remove the fuses (or trip the circuit breaker) on your 3-phase supply.
Parameter
Description
ENCODER INVERT
Encoder direction
MAG CURRENT
Magnetising current
STATOR RES
Per phase stator
resistance
LEAKAGE INDUC
Per phase stator
leakage inductance
MUTUAL INDUC
Per phase mutual
inductance
ROTOR TIME
Rotor time constant
CONST
890SD Standalone Drive
WARNING
Note
Parameter is only set up if drive is
configured to run as Closed-loop Vector
Not measured by Stationary Autotune
Not measured by Stationary Autotune
This is identified from magnetising current
and motor nameplate rpm
4-53